Relay test set S100A Brochure0 pages
PONDVP
nnnnSingle Phase Relay Tester
nnnnModel S100A
nnnnSpecifications
nnnnVoltage generators
nnnnrange
nnnnFrequency
nnnn40Hz~60Hz
nnnnPhase angle
nnnn0-359.9°
nnnnAC voltage
nnnn3X0-120V
nnnnAC current
nnnnSource 1 0A-100A
nnnnSource 2 0mA-200mA
nnnnDC voltage
nnnn0-300V (through Uab)
nnnnDC current
nnnnSource 1 0A-10A
nnnnSource 2 0mA-200mA
nnnnAuxiliary DC
nnnn0V/110V/220V
nnnnResponse time for V and I < 100 us
nnnnOutput power
nnnnAC Voltage
nnnnMax. 60VA
nnnnAC Current
nnnnMax. 800VA
nnnnAuxiliary DC
nnnnHOW at 220V
nnnnBinary output
nnnnNumber
nnnn1
nnnnType
nnnnDry contact
nnnnBreak capacity AC Vmax : 250V(ACyimax : 0.5A
nnnnBreak capacity DCVmax : 250V(DCyimax : 0.5A
nnnnDimension and weight_
nnnnAluminum casing_
nnnn364mmxl55.5mmx415mm(WxHxD) 18kg
nnnnAC voltage
nnnnRange
nnnn0V-1V 1V-2V 2V-120V
nnnnAccuracy
nnnn±5mV ±0.5% ±0.2%
nnnnAC current
nnnnRange 0-200mA(source 2) 0A-1A 1A-2A 2A-40A
nnnnAccuracy_±0.4mA ±5mA ±0.5% ±0.2%
nnnnDC voltage
nnnnRange
nnnn0V-5V
nnnn5V~300V
nnnnAccuracy
nnnn±20mV
nnnn±0.5%
nnnnDC current
nnnnRange_0-200mA (source 2) 0.2A-1A 1A-10A
nnnnAccuracy_±0.2mA ±5mA ±0.5%_
nnnnAuxiliary DC accuracy
nnnn±1%
nnnnl'hase angle accuracy
nnnn• 0.2"
nnnnI 'Ycquency accuracy
nnnn±2mHz
nnnnBinary inputs
nnnnNumber
nnnnType
nnnn15V-250V(DC) or potential free
nnnnSample rate
nnnn5KHz
nnnnResolution
nnnnlms
nnnnDebounce time
nnnn20ms
nnnnIsolation
nnnnIndependent gavarnic isolation
nnnnPower supply
nnnn110/220V±15% 50Hz 10A
nnnnPONOVO POWER CO., LTD.
nnnn2F,4Cell, TowerC, In.Do Mansion.No.48A Zhichun Road, Haidian DistrictBeijing. PR China (100098)
nnnnTel.+86 (10) 8275 5151 (reception) Tel. +86 (10) 8275 5151ext.8887
nnnnFax.+86 (10) 8275 5151-8103 info@ponovo.com.cn www.ponovo.com.cn
"