Single Phase Relay Test Set T200A0 pages
PW460 Specification
T500 Series
Universal Tester
Model T200A
Specifications
High power AC current output (I1)
Range
Accuracy
Output voltage
Power
Load time
Output
Time
0.2A~8A
1A~40A
±0.5%
40 V~ 30 V
1200VA( 40 A)
150 V~ 100 V
800VA( 8 A)
250 A
120s
100 A
750s
10~250A
10 V~8V
2000 VA(250A)
50A
<50A
3000s continuous
High power AC voltage output (U1)
Features :
Constant current design
Long output time at 250A (120s)
Can test all types high burden relay
Automatic local test modules, such as df/dt,
ramp, pick up, time, harmonic restraint
check, directional relay, etc
In-built CT test functions
Test results can be transferred to external PC
High precision AC/DC current output (I3)
Range
Accuracy
Power
Load time
Mode
AC output
0~200mA
Range
±0.5%
Accuracy
75Ω
Power(200mA)
20~100Hz
Frequency
<1A :
1~3A :
10~500V
±0.5%
1200VA(400V)
continuous
Max 60min
High power DC voltage output (Udc)
Range
Accuracy
Power (300V)
Load time Output :
Time :
10~300V
±0.5%
600W
< 1A
continuous
>1A
Max 60min
DC output
0~200mA
±0.5%
75Ω
—
Binary inputs
2
Number
30~250V DC, or dry contact
Input characteristics
±1ms ( 0.001~1s ) ±0 . 1%(1~9999.999s)
Time resolution
9999.999s
Max. measuring time
Binary output
Auxiliary DC voltage output (Aux Udc)
Range
Accuracy
Power
Load time
20~240V
± 1%
55W at 110V/110W at 220V
continuous at 0.5A
Number
Type
Break capacity AC
Break capacity DC
1
Potential free relay contacts
Vmax 250V AC / Imax 8A / Pmax 2000VA
Vmax 250V DC/ Imax 8A / Pmax 150W
Power supply
AC/DC current output (I2)
Nominal input voltage
Permissible tolerance
Nominal frequency
Permissible frequency
Mode
AC output
DC output
0~20A
0~20A
Range
±0.5%
±0.5%
Accuracy
200VA
200W
Power(20A)
20~420Hz
—
Frequency
0~360°
—
Phase angle
0.5 °
—
Phase angle accuracy
—
Distortion 1A~20A <0.5%
500μs
500μs
Transient response
60s
Load time 20A :
240s
10A :
continuous
<10A :
1%
Harmonic(2nd,3rd,5th,7th)accuracy
Range
Accuracy
AC/DC voltage output (U2)
EMC (Emission)
EMC (Immunity)
Safety
110/220Vac
-20% ~+15%
50/60Hz
45~65Hz
Voltmeter
0~600V AC/DC
± 1%
Ammeter
Range
Accuracy
0~6A AC/DC
±1%
Certificates
www.ponovo.com.cn
Mode
AC output
0~120V
Range
±0.5%
Accuracy
60VA
Power(120V)
20~100Hz
Frequency
0~360°
Phase angle
0.5 °
Phase angle accuracy
<0.5%
Distortion 5V~120V
500μs
Transient response
DC output
0~120V
±0.5%
60W
—
—
—
—
500μs
IEC-61000-3-2/3
IEC 61000-4-2/3/4/5/6/11
IEC 61010-1
Others
Operation temperature
Operation humidity
Weight
Dimensions (W x H x D)
PC connection
Ground Socket (earth)
-5 ~ +50°C
5 ~95 %, non-condensing
20.7kg
430 mm×250mm×250 mm
USB
4 mm banana socket; front side