CT Analyzer?PCT 200Ai?0 pages
PCT200Ai CT/PT Test System
More than 20 CT
tests can be performed
automatically in one time
Main Features
Can test M/P/TP type, bushing and GIS type CT
Ratio check up to 30 000 : 1 and 45 000 : 5
Knee point check up to 40 000V
Standards : IEC60044-1, IEC60044-6, ANSI/IEEE C57.13
Results saved directly in Excel format
Report can be transferred to flash disk via USB port
Weight : 11kg
Following PT tests
can be done automatically
Polarity
Ratio
Excitation
Burden
Burden
Winding resistance
Excitation
Polarity
Ratio
Ratio error and phase displacement
Saturated inductance (Ls)
Unsaturated inductance (Lu)
Remanence flux (Kr)
Secondary time constant (Ts)
Accuracy limiting factor (ALF)
Instrument security factor (FS)
Transient dimensioning factor (Ktd)
Peak instantaneous error (ε )
Composite error
Demagnetization
Winding resistance measurement
Output voltage range
Output current range
Output power
Ratio measurement
Phase measurement
Current measurement
Voltage measurement
0~120V
0~5Arms (15A peak)
0.0001VA~500VA RMS (1500VA peak)
30000:1 or 45000:5
±0.02% Typ. ±0.05% Gur.
1min Typ. 2min Gur.
0.01min
range: 0~15 A (auto ranging)
±0.02% Typ. ±0.05% Gur.
range: 0~120V (auto ranging)
accuracy: ±0.02% Typ. ±0.05% Gur.
Burden measurement
Communication port
Dimemsion
Weight
Main supply
Operation temperature
range: 0.05~200Ω
accuracy: 0.1% +1 mΩ
±0.05%±1mΩ Typ. ±0.1%±1mΩ Gur.
range: 0.05 ~200Ω
accuracy: 0.1 % +1mΩ
±0.05%±1mΩ Typ. ±0.1%±1mΩ Gur.
USB
470*200*245mm (WxHxL)
11kg
110-240Vac/50-60Hz (norminal)
90-260Vac/45-65Hz (permissible)
-10-50° C
POWER ADVANCED TECH. CO., LTD.
2F,4Cell, Tower C, In.Do Mansion,No.48A Zhichun Road, Haidian DistrictBeijing, PR China (100098)
Tel. +86 (10) 8275 5151(reception)
Tel. +86 (10) 8275 5151ext.8887
Fax. +86 (10) 8275 5151-8103 info@ponovo.com.cn www.ponovo.com.cn
Subject to modification without notice. Revised in Feb 2011
Technical specifications