PCT200i CT PT Tester0 pages
PONDVD
PCT200i CT/PT Test System
Main Features
• Can test M/P/TP type, bushing and GIS type CT
• Ratio check up to 30 000 : 1 and 45 000 : 5
• Knee point check up to 30 000V
• Standards : IEC60044-1, IEC60044-6, ANSI/IEEE C57.13
• Results saved directly in Excel format
• Report can be transferred to flash disk via USB port
• Weight: 11kg
Following PT tests
can be done automatically
• Polarity
• Ratio
• Excitation
• Burden
More than 20 CT
tests can be performed
automatically in one time
• Burden
• Winding resistance
• Excitation
• Polarity
• Ratio
• Ratio error and phase displacement
• Saturated inductance (Ls)
• Unsaturated inductance (Lu)
• Remanence flux (Kr)
• Secondary time constant (Ts)
• Accuracy limiting factor (ALF)
• Instrument security factor (FS)
• Transient dimensioning factor (Ktd)
• Peak instantaneous error (e")
• Composite error
• Demagnetization
Technical specifications
Output voltage range
Output current range
Output power
Ratio measurement
Phase measurement
Current measurement
Voltage measurement
0-120V_
0-5Arms (15Apeak)
0.0001VA~500VARMS (1500VApeak)
30000:1 or 45000:5
0.05%Typ. 0.1%Gur
lmin Typ. 3min Gur.
O.lmin
range: 0—15 A (auto ranging)
±0.05% Typ. ±0.10% GurT
range: 0-120V (auto ranging)
accuracy: ±0.05% Typ. ±0.10% Gur.
Winding resistance measurement
range: 0.05~200n_
±0.05%±lmnTyp. ±0.1%±lmn Gur.
Burden measurement
range: 0.05~200n_
±0.05%±lmn Typ. ±0.1%±lmn Gur.
Communication port
Dimemsion
USB_
470*200*245mm (WxHxL)
Weight
Main supply
14kg_
110-240Vac/50-60Hz (norminal)
90-260Vac/45-65Hz (permissible)
Operation temperature
-10-50° C
IPONOVO POWER CO., LTD.
2F,4Cell,TowerC, In.Do Mansion,No.48A Zhichun Road, Haidian DistrictBeijing, PR China (100098)
1 Tel.+86(10)8275 5151 (reception) Tel.+86 (10) 827551 51 ext.8887
-ax.+86(10) 8275 5151-8103 support@relaytest.com info@relaytest.com www.relaytest.com
"