Relay test set PW466i0 pages
PW460 Specification
PW466i
Universal Test System
Specifications
Voltage generators
Binary outputs relay
Accuracy
Setting range
6-phase AC( L-N)
1-phase AC( L-L)
dc (L-N)
6 × 0~150V
1 × 0~300V
6 × 0~±150V
Power
6-phase AC(L-N)
6 × 30VA at 150V
3-phase AC(L-N)
3 × 60VA at 150V
1 × 100VA at 300V
1-phase AC(L-L)
6 × 40 W at ± 150 V
dc (L-N)
Accuracy
error < 0.0 8 % rd .+0. 02 %
rg . guar. at 0~ 15 0 V
error < 0.04 % rd .+0. 01 %
rg . typ. at 0~ 15 0 V
150V
Ranges
Resolution
5mV for 150Vac
Distortion
< 0.05 % typ., (< 0.1 % guar.)
Current generators
Setting range
6-phase AC(L-N)
3-phase AC(2L-N)
1-phase AC(6L-N)
dc(L-N)
dc(6L-N)
Power
6-phase AC(L-N)
3-phase AC(2L-N)
1-phase AC(6L-N)
6×180VA typ., at 20A
6×150VA guar., at 15A
3×320VA typ., at 40A
3×240VA guar., at 30A
1×600VA typ., at 120A
1×450VA guar., at 90A
1×450VA typ., at 30A
15Vpk/32Vpk
6×100W at ±10A
1×480W at ±60A
4
Potential free relay contacts,
software controlled
Break capacity ac
Break capacity dc
Vmax: 300Vac /Imax:
8A /Pmax: 2000VA
Vmax: 300Vdc /Imax:
8A /Pmax: 150W
In-built monitoring and recording
General
Frequency
Sine signal
Transient signal
Accuracy
Resolution
Number
Type
DC,1~2000Hz
DC~10.0 KHz
± 1ppm
0.001 Hz
Phase
Angle range
- 360º~+360º
Accuracy <0.05º typ.,<0.1º guar.at 50/60Hz
Resolution
±0.001º
Auxiliary dc supply
0~ 300V
88W at 110V, 176W at
220V, 120W at 300V
Accuracy error < 0.1 % rg. typ. (<0.5 % rg. guar.)
Voltage range
Power
Binary inputs
8
Number
Input characteristics 0~400Vdc threshold or
potential free
100μs
Time resolution
infinite
Max. measuring time
Debounce/Deglitch time
0~25ms
Counting function
< 3kHz at pulse
width>150μs
05
currents and voltage outputs
Monitoring
Recording analog outputs, binary inputs/outputs status
Mode real time monitoring, no external wiring is required
Recording length
16s
Power supply
Nominal input voltage
Permissible input voltage
Nominal frequency
Permissible frequency
110~240Vac
90~260Vac
50/60Hz
45~65Hz
IEC61850 upgrade
Interpretation hardware is in-built. Please contact the
supplier for options to activate the IEC61850 software
support function
Environmental conditions
Operation temperature
Storage temperature
Relative humidity
EMC (Emission)
EMC (Immunity)
Safety
0~+50ºC
-25~+70ºC
5~95% non - condensing
IEC-61000-3-2/3
IEC 61000-4-2/3/4/5/6
IEC 61010-1
Others
PC connection
GPS interface
Ground Socket (earth)
Weight
Dimensions (W x H x D)
Ethernet10M/100M
DB9/TTL
4 mm banana socket; front side
20kg
360mm × 157mm× 367mm
PONOVO POWER CO., LTD.
2F,4Cell, Tower C, In.Do Mansion,No.48A Zhichun Road, Haidian DistrictBeijing, PR China (100098)
Tel. +86 (10) 8275 5151(reception)
Tel. +86 (10) 82755151ext.8887
Fax. +86 (10) 8275 5151-8103 support@relaytest.com
info@relaytest.com www.relaytest.com
subject to modification
1-phase AC(L-L)
Max compliance
voltage(L-N)(L-L)
dc(L-N)
dc(6L-N)
6×0~20A
3×0~40A
1×0~120A
6×0~±20A
1×0~±120A
Ranges
Resolution
Distortion
error < 0. 15 % rd .+0. 05 %
rg . guar. at 0~ 2 0 A
error < 0.0 8 % rd .+0. 0 2 %
rg . typ. at 0~ 2 0 A
20A or 40A
1mA
< 0.05 % typ. (< 0.1 % guar.)