OWWG3 Oil Water alarm unit Riels0 pages
OWWG3
OIL/WATER
ALARM UNIT
LEVEL
Oil/water alarm unit ÖWWG 3
•t
•t
•t
•t
For storage rooms, manholes, drip pans
With visual/audible alarms, Test/Acknowledge buttons and relay
output
Self-monitoring probe
EnOcean®-ready
Applications
For visual and audible alarms if liquids with a flash point of ≥ 55°C are
detected in, for example, oil storage rooms, drip pans, inspection ducts,
ducts, protective pipes, manholes, pipes and cellars.
Suitable for the following media: water, fuel oil EL, L or M, diesel fuel or
low-viscosity lubricating oils, motor oils, hydraulic oils, vegetable oils and
transformer oils, antifreeze agents, oil-water mixtures and emulsions. Use as
leak detection system class III as per EN 13160-1/-4 and as leak detection
system as per TRWS 791-1.
Tutti i dati ed i contenuti di questa scheda sono di proprietà esclusiva di Riels Instruments
Description
The oil/water alarm unit in a wall mounting housing triggers visual and
audible alarms in the event of accumulations of liquids which can be caused
by tank leaks, backflow, flooding, etc. ÖWWG 3 consists of a control unit
with visual/audible alarm,Test and Acknowledge buttons as well as a flexible
PTC thermistor probe. The probe is mounted at the lowest point of the
area to be monitored. The alarm is triggered when the probe comes into
contact with liquid. The audible alarm can be muted with the Acknowledge
button. The visual alarm remains active until the leak has been fixed.
The Test button allows you to simulate an alarm condition in order to
perform a function check. The self-monitoring probe triggers an alarm if
it is damaged. The voltage-free relay contact is provided for connection
of additional alarm equipment (such as additional alarm unit ZAG 01).
ÖWWG 3 is suitable for panel mounting with a mounting frame. A sealing
kit (IP 54) is available for rough application conditions. Alarm units can
be integrated into your existing building automation systems at lug the
wireless module into the interface (PCB of the device). The Gateway in
conjunction with additional RIELS products with wireless technology allow
you to configure a whole range of fully customisable, extensible features for
the protection of plants and buildings.
Technical specifications
Fluid:
Water
Probe:
L x Ø: 57x14 mm
Cable length: 3.2 m or 10 m
Standard probe cables:
1.5 m, max. length 50 m (shielded)
Operating temperature range:
Ambient -5/+40°C
Supply voltage:
AC 100–240 V or AC/DC 15–40 V
Nominal power:
10 VA
Switching output:
Relay contact: 1 voltage-free changeover contact
Contact rating:
Max. AC 250 V, 2 A
Alarm sound:
Min. 70 dB(A)
Housing:
Wall mounting housing made of impact-resistant plastic (ABS)
W x H x D: 100x188x65 mm
Degree of protection: IP 40 (EN 60529)
Scope of delivery:
Control unit
PTC thermistor probe
Option:
EnOcean® wireless module (can be retrofitted)
Riels Instruments Srl
+39 049 8961771
+39 049 717368 www.riels.it info@riels.it
"