SLA3.1000 pages
AS-Interface
Power Supply with 2.8A
Data sheet
SLA3.100
•
•
•
•
•
Input: AC 115V / 230V
Output: 30.55V / 2.8A
AS Interface data decoupling
Infrared (IR) addressing mode
For highly demanding industrial
applications
• NEC Class 2 Power Supply
EMC and
Low Volt.
Directive
UL508 LISTED
IND. CONT. EQ.
18 WM, 60°C
Appr. No. 34301
CB
scheme
IEC60950
Short description
Data and energy:
The primary switched mode DIN rail power supply SLA3.100 specifically
supplies AS Interface® systems with energy. The AS-Interface bus technology allows to connect up to 62 participants to a control and to supply
them with energy with a single two-conductor cable. When connecting
slaves, the yellow AS-Interface cable offers the high degree of protection
IP67 in conjunction with the insulation displacement. The communication signals of the individual network participants are modulated onto
the supply voltage. For this purpose, specific power supply units with integrated data decoupling are required for AS-Interface systems.
munication on the yellow AS-Interface cable. Participants with an infrared interface can then quickly be assigned a new ID address by means of
an infrared programming unit without the need to disconnect them
from the AS-Interface cable. Afterwards, the "Communication Mode"
can be selected again to re-start the data communication.
Fit for the world market:
The input voltage range of the unit can be selected on the front panel.
Thus, it can be operated worldwide on all usual single-phase line voltages. International (IEC 60950) and various national (CBscheme) approvals
allow for worldwide application.
Fast addressing of slaves:
The "IR addressing mode" selectable via jumper interrupts the data com-
Input
Output
Rated voltage
AC100-120/220-240V
(selectable by front panel slide switch)
Rated current
2.0A (switch in 115V position)
0.9A (switch in 230V position)
Frequency
47...63 Hz (alternatively DC also possible)
Voltage range
AC 85...132V/184...264V, DC 230...375V
Power factor
>0.5
Harmonic current
emissions
EN 61000-3-2 [PFC], Class A limits are fulfilled
Rated current
2.8A
Isolation
Safe low voltage
Current limitation
>3.2 A
PELV (IEC364-4-41)
SELV (IEC60950)
Inrush current
limited by NTC resistor
Tamb = +50°C, cold start (line impedance
acc. EN 61000-3-3)
20A (AC 132V) / 38A (AC 264V)
1.5 A2s (AC 132V) / 1.8 A2s (AC 264V)
>26 ms @ AC 100V or 196V and rated load
(also see diagram)
Overload behaviour
Continuous current (also see diagram)
min. 3.2A, max. 4.6A
Load regulation
stat. <200mV (no load / full load)
Line regulation
stat. <10mV (AC 85...132V/184...264V)
Ripple
T2A5 / 250V HBC (not accessible)
Hold-up time
DC 30.55V ±3% (not adjustable)
Short-circuit current
Integrated internal
fuse
Peak current Ipk
I2t
Rated voltage
<50 mVPP (500kHz bandw., 50Ω measurem.,
ohmic load)
Noise (Spikes)
<100mVPP (20MHz bandw., 50Ω measurem.,
ohmic load)
Over-voltage protection max. 55V
Operating indictor
Green LED (extinguishes at overload)
Output is protected against short-circuit, open circuit and overload.
Use AS-Interface power supplies only together with AS-Interface lines.
Order information
Order number
sla3e100 / 040511
Description
SLA3.100
SLZ11
SLZ02
AS-Interface power supply unit
Adapter for S7-300 rail
Wall mounting set (two pcs. per package)
1/4