XT40.3620 pages
XT40.361, XT40.362
36V, 26A, THREE-PHASE INPUT
– X-Series
SEMI-REGULATED POWER SUPPLY
•
•
•
•
•
•
•
•
•
•
•
•
•
1. GENERAL DESCRIPTION
Alternative or Replacement for AC Transformer
Three Phase Input – DC Output
DIN-Rail Mountable
Width only 96mm
95.5% Efficiency
125% Peak Power Capability
No Input Inrush Current
Active Input Transient Blocker
Full Power Between -25°C and +60°C
Easy Failure Diagnostics
No Electrolytic Capacitors on Input Side
Cost Effective and Robust
3 Year Warranty
2. SHORT-FORM DATA
Primary use are applications involving supplies to
motors, valves and other load circuits with a high
power consumption, where an accurate output
voltage regulation which is standard on traditional
switched-mode power supplies is not required.
Furthermore, these switched-mode power supplies
can often replace mains transformers with rectifiers.
DC 36V
none
26.6A
33.3A
Output power
960W
1200W
Output ripple
< 2000mVpp
< 250mVpp
Input voltage
3AC 400V
3AC 480V
Mains frequency
50-60Hz
AC Input current
1.65A / phase
1.4A / phase
Power factor
0.93
AC Inrush current
typ. 2A peak
Efficiency
95.5%
Losses
45.2W
Temperature range -25°C to +70°C
Derating
24W/°C
Dimensions
96x124x159mm
3. ORDER NUMBERS
4. MARKINGS
The power supplies in the Dimension X-Series include
a new and innovative concept for generating an
isolated DC voltage from a three-phase mains
system.
A semi-regulated resonant converter enables a very
compact design, maximum efficiency and extremely
competitive pricing with only a small compromise in
the output voltage regulation, output ripple and
hold-up time.
Weighing just 1.4 kg, the device provides 960 watts
of continuous output power and an additional 25%
power reserve for dynamic loads. The light-weight
design along with compact dimensions facilitate
straightforward mounting on DIN-rail.
Power Supply
XT40.361
XT40.362
400V Input
480V Input
Output voltage
Adjustment range
Output current
continuous
for typ. 15s
continuous
for typ. 15s
20Hz-2kHz
2kHz to 20MHz
XT40.361
XT40.362
±6%
XT40.361, 3x400V
XT40.362, 3x480V
36V, 26.6A
operational
+60 to +70°C
WxHxD
18WM
LISTED
IND. CONT. EQ.
UL 60950-1
UL 508
Jan. 2007 / Rev. 1.0 DS-XT40.36x-EN All parameters are specified at 36V 13.3A, 3x400Vac (XT40.361) or 3x480Vac (XT40.362),
25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0
Germany
EMC, LVD