TG 1000 pages
Technical Data Sheet
Temperature transmitter
New
TG 100
TG 100
duct mount
• Duct temperature transmitter, TG100 type
• Measuring ranges from 0 to +50°C, -20 to +80°C, -50 to +50°C, 0 to +100°C,
0 to 200°C, 0 to +300°C, 0 to +400°C (according to model, see “Configuration”)
• 0-10 V output , active sensor, power supply 24 Vac/Vdc (3-4 wires) or
4-20 mA output , passive loop, power supply 18 to 30 Vdc (2 wires)
• ABS IP 65 housing, with or without display
• Quick and easy mounting “1/4 turn” system with wall-mount plate
TG 100
Pt 100 on terminal block
(probe in option)
Features of the transmitter
Temperature
Part number
To order, just add the codes to complete the part number :
Working principle : Pt100 is a resistance with a positive temperature
coefficient which varies according to the temperature. The higher the
temperature is, the more the value of the resistance increases.
Example : for 0°C 100 - for 100°C 138,5
Transmitter / power supply / output
V
A
Measuring range ......................see chart ”Configuration”
Units of measurement .............°C, °F
Accuracy * ................................±0,5% of reading ±0,4°C (duct mount probe)
according to the probe (Pt 100 on terminal block)
Response time .........................1/e (63%) 5 sec. (duct mount probe)
according to the probe (Pt 100 on terminal block)
Resolution ................................0,1°C
Type of sensor..........................Pt 100 class A as per DIN IEC751
Type of fluid............................ air et neutral gases
Active • 24 Vac/Vdc • 0-10V
Passive • 18/30 Vdc • 4-20 mA
Display
O
N
With display
Without display
Mounting
A
B
Duct mount
Terminal block
WITH or WITHOUT display
-
TG100
Features of the housing
Example : TG100-VOA
Model : temperature transmitter TG 100 active sensor 0-10 V output, with
display and duct mount probe.
Housing ...............................................ABS
Fire-proof classification.....................HB as per UL94
Dimensions ........................................see drawings beside
Protection............................................IP 65
Display.................................................5- digit LCD. Dimensions 50 x 15 mm
Height of the digits .............................10 mm
Cable gland .........................................for cables Ø 8 mm maxi.
Weight..................................................151 g (with display) - 116 g (without display)
Dimensions of the housing
(with wall-mount plate)
Pt100 on terminal block
99 mm
Technical Specifications
109 mm
42 mm
Duct mount
Output / power supply....active transmitter 0-10 V (power supply 24 Vac/Vdc ±10%), 3-4 wires
..........................................passive loop 4-20 mA (power supply. 18/30 Vdc), 2 wires
..........................................maximum load : 500 Ohms (4-20 mA)
..........................................minimum load : 1 K Ohms (0-10 V)
Consumption ....................................2 VA (0-10V) or max. 22 mA (4-20mA)
Electro-magnetical compatibility .......EN 61326
Electrical connection .......................screw terminal block for cables Ø 1.5 mm² max
Communication to PC ...................... Kimo RS 232 cable
Working temperature (housing) ..........0 to +50°C
Working temperature (probe) .............-20 to +80°C (duct mount probe)
99 mm
42 mm
Ø 13 mm
109 mm
125 mm
according to the probe (Pt100 on terminal block)
Storage temperature ........................-10 to +70°C
Environment .....................................air and neutral gases
*All the accuracies indicated in this technical datasheet were stated in laboratories conditions, and can be guaranted for
measurements carried out in the same conditions, or carried out with calibration compensation.