Lampak UFO-3AW specification sheet0 pages
UFO-3AW
Emergency Lighting Fluorescent Battery Pack
Catalog Number
FEATURES
Comments
Type
Application
The UFO-3AW emergency battery pack works in conjunction with
a fluorescent fixture’s normal AC ballast to convert new or existing
fluorescent fixtures for emergency lighting operation, eliminating the
need to install additional emergency lighting units. The UFO-3AW can
be used with one 32W through 40W (2’ - 4’) T8, T10, or T12 fluorescent
lamp without integral starters, including U-shaped, HO, VHO and
circline. It is also compatible with most 1, 2, 3, and 4-lamp electronic,
standard magnetic, end-of-lamp-life and dimming AC ballasts. If
used in an emergency-only fixture, no AC ballast is necessary. For
information about specific lamps and ballast compatibility, please
contact the factory.
Construction
All unit housings consist of a compact case constructed of 22 gauge
sheet metal finished in black enamel. The unit contains a solid-state
charger with automatic transfer circuit, test switch, LED charge indicator
light, a dependable, high-frequency inverter and a high-temperature,
Nickel-Cadmium battery.
Installation
Model UFO-3AW emergency battery pack does not affect normal
fixture operation and may be used with either a switched or unswitched
fixture. If a switched fixture is used, an unswitched hot lead must be
connected to the emergency battery pack. The emergency battery
pack must be fed from the same branch circuit as the AC ballast. The
UFO-3AW may be installed inside, on top of, or remote from the fixture.
The emergency battery pack may be remotely installed up to half the
distance from the lamp the AC ballast manufacturer recommends, or
up to 50 feet, whichever is less. UFO-3AW emergency battery packs
are not suitable for installation in heated air outlet fixtures and wet
or hazardous location fixtures. Installation is not recommended with
fixtures where the ambient temperature may fall below 0°C (32°F).
Illumination
The UFO-3AW produces 350-450 lumens initial emergency light
output. During emergency illumination, one lamp is illuminated, even if
installed with a multi-lamp fluorescent fixture.
Compliances
UL 924 Damp Location Listed
NFPA 101 (Life Safety Code)
NFPA 70 (National Electrical Code)
Warranty
5 Years Full Warranty
ORDERING GUIDE
UFO-3AW
Model
ACCESSORIES (ORDER SEPARATELY)
F-WC
Wiring bundle cover(1)
SPRTS
Remote test switch/charge
indicator module(2)
(1)t Encloses exposed wiring harness when power pack is externally mounted on the
t lighting fixture. One required per fixture.
(2)t Fits single-gang box.