D Series
Single-Phase Central Lighting Inverters
Catalog Number
Comments
FEATURES
Type
Application
Designed for indoor installation in commercial or industrial applications.
Operation
When normal utility-supplied power is present, the LSN model central lighting inverter
provides load-side line conditioning with "brownout" protection, and charges the system
batteries when required. When utility-supplied power is interrupted, or the voltage varies
from predetermined limits, the system will automatically and instantaneously transfer to
emergency mode without interruption to connected loads. DC battery-derived emergency
power is inverted to AC power and supplied in a pure sine wave output form for 90 minutes
(standard run time). A low voltage battery disconnect circuit prevents “deep discharge”
damage to the batteries during prolonged power outages. When normal power is restored
the system will automatically restart, providing power to connected loads and recharging
the batteries. The charging circuit will bring the batteries to full recharge within UL time
standards.
Construction
The LSN cabinet is constructed of steel, finished with a light gray paint and features
locking cabinetry and password-protected user interface for security. Louvers at front
and top of cabinet allow venting.
ORDERING GUIDE
Dt 277t01t
Series
LSN Central
Lighting Inverter
Input Voltage
(VAC)
tt
120(16)
208
240
277
347
(1)t
(2)t
(3)t
(4)t
(5)t
(6)t
t
t
(7)t
(8)t
(9)t
(10)t
(11)t
(12)t
t
t
(13)t
t
t
(14)t
(15)t
(16)t
St 120t Nt
Bt 20t 02t Ut - RSP
Battery Type
Capacity
Rating
01 = 1.0KVA
02 = 2.0KVA
27 = 2.7KVA
37 = 3.7 KVA
48 = 4.8 KVA
55 = 5.5 KVA
66 = 6.6 KVA
83 = 8.3 KVA
10 = 10.0 KVA
12 = 12.5 KVA (1)
15 = 15.0 KVA (1)
17 = 17.5 KVA (2)
S =t10-year Sealed
tLead-Calcium
G =t20-year Sealed
tLead-Calcium
N =t25-year Nickel-t
tCadmium
Output Circuit
Breaker Ampere
Rating (7)
Output Circuit
Breaker Type
Blank = Normally On
N = Normally Off
Output
Voltage (3, 4)
(VAC)
120
240
120/208
120/240 (5)
120/277
277
347
Requires a provided external transformer for 208VAC or 240VAC input.
277 and 347VAC input only.
Other voltages available. Consult factory.
External transformer may be provided.
Loading may not exceed 50% of the system’s total rating on any 120VAC leg.
Normally On circuit breakers: a maximum of 14 monitored, single pole positions or
20 unmonitored, single pole positions may be specified. Normally Off circuit breakers: a
maximum of 8 single pole positions (monitored or unmonitored) may be specified.
Normally Off circuit breakers: a maximum rating of 20 amps.
The EPO option requires the SMT option.
Specify runtime in minutes when ordering. Example: AR120.
Available with 1.0, 2.0, 2.7, 3.7, 5.5, and 6.6KVA Series with S batteries only.
Available on 1.0 KVA - 4.8KVA Series.
Available on 5.5 KVA - 17.5KVA Series. Not available with 120V input on 6.6KVA and
above. Not available with 208V input on 12.5 KVA and above. Not available with 240V
input on 15.0 KVA and above.
Supplied in a wall mounted, NEMA 1 type enclosure. Cannot be used in systems with
more than one single-pole output circuit breaker, on systems with different input and
output voltages.
See System Configuration for 90-Minute Run Time.
Type S Battery only; See system configuration for 90-minute run time.
Not available on 8.3KVA - 17.5KVA Series.
Output Circuit Breaker
Supervision
Blank = Monitored
U = Unmonitored
15t 30t50
20t 35t60
25t 40t80
Output Circuit
Breaker Voltage
Rating
A = 120 VAC
B = 240 VAC
C = 277 VAC
D = 208 VAC
Output Circuit
Breaker Quantity (6)
01 to 20
Other Options & Accessories
Options
EMLt =t Email Device
RSPt =t Remote Status Panel
SMTt =t System Monitoring
ttTerminal
EPOt =t Emergency Power Off
ttTerminal (8)
ARt =t Alternate Runtime (9)
SBCt =t Short Battery Cabinet (10)
IBSt =t Internal Maintenance
tt Bypass Switch
tt (Make Before Break)
C10t =t 10 Amp Charger
ttUpgrade (11)
C20t =t 20 Amp Charger
ttUpgrade (12)
CL60t=t Cabinet Locks
St
=t Seismic Qualified(15)
Accessories
MBBt =tt External Maintenance
ttt Bypass Switch (13)
ttt
(Make Before Break)
BBMt =tt External Maintenance
ttt Bypass Switch (13)
ttt
(Break Before Make)
DSFK__ =t Seismic Kit (14)
t