LR056 Pressure Tranducer Displays0 pages
Data Sheet
DS-PR-LR-056-PD-eng
February, 2012
Brooks® LR-056
Brooks® LR-056 Transducer Display
Accurate, miniature displays for point-of-use pressure monitoring
Description
Local display of process pressure improves safety and
quality control of gas delivery systems. The LR-056 allows a
4-20 mA sensor to digitally display its pressure and send its
signal to a final destination. The sensor, such as the Brooks®
SolidSense II® pressure transducer, connects to the back of
the LR-056 with a 4-pin Bendix® connector. The LR-056
connects to the loop through a 2-wire pigtail cable. The LR056 offers a real time reading. This device is loop powered
and single channeled. The LR-056 has two user
programmable setpoints which define a window - if the
window is entered or left an output signal is generated.
Features and Benefits
• Local indication of process pressure measurement
• 4-digit LED display in durable metal enclosure
• Available to display pressure measurement in PSIA,
PSIG, Bar, Kg/cm2 or Mpa
• Setpoint indication and contact switching available
• Password protected
• RoHS and CE (EN 61326) compliant
• Programmable via up and down switches
• Point-of-use monitoring
• Extremely accurate reading with outstanding noise
immunity
• Low power electronics
• Ease of use and installation
Applications
Gas delivery systems and tools including:
• Gas Cabinets
• Gas Panels
• Bulk Gas
Specifications
Performance
Display:
Type:
Range:
Polarity:
Decimal Point:
Accuracy:
Digital Damping:
Value Update:
Conversion Rate:
Temp. Coefficient:
Mechanical
Material:
Digit Height/Width:
Pigtail Length:
4-digit, red LED with 7 segments
-1999 to +9999
Automatic (-) displayed in vacuum
Adjustable by customer
+0.1% full scale +1 digit
0.3 to 30 sec. (programmable)
0.1 to 10 sec. (programmable)
10 times / second
+0.01% F.S. / OC
Aluminum, black anodized
7mm / 4.85mm
2m standard (optional length
available on request)
Stability
Vibration:
10g RMS (20 to 2000 Hz)
Shock:
100g / 11 msec
App. Shipping Weight: 200g
LR-056 Pressure Transducer Display
Electrical
Power Requirements:
Current loop powered
(transducer voltage +6 Vdc
loop voltage drop)
Input:
4-20 mA (2-wire, loop powered)
Connections:
Back mount: 4-pin female Bendix®
Input:
connector; factory wired for
4-20 mA Transducer
Output:
Top mount: 6-wire cable
Pressure Warnings:
Optional 1 or 2 warnings,
programmable in a window with
2 limits
Setpoint Contact Rating: Imax = 50 mA, Vmax = 24 Vdc,
electrically isolated
Resistive Load:
Rmin = 450 Ohm @ 24 Vdc
Power:
Pmax = 200 mW
Inductance:
4.7 mH
Switching Cycles:
>100M
Delay Time:
0 to 100 sec.
Protection:
Short:
Reverse:
Access:
Data Storage:
Environmental
Temp Range:
Operating:
Storage:
Compliance:
CE:
RoHS:
Permanent short-circuit
protection
No damage at reverse polarity,
but, no function
Protection available
Non-volatile EEPROM, min/max
value memory
-13 to 185OF (-25 to 85OC)
-40 to 185OF (-40 to 85OC)
Compliant to EMC
Directive EN61326
Compliant to RoHS Regulations