NT210+TPL2100 pages
NT210 + TPL210 TECSYSTEM „7.
nnnnTemperature protection relays & ventilation
nnnnThe NT210 unit and the TPL210 sensor represent the most innovative system on the
nnnnmarket for the monitoring of oil hermetic transformers!
nnnn•C T
nnnnmBar P
nnnn|TEST| (MODE]
nnnnCOMPLETELY ELECTRONICALLY!
nnnnThe electromechanical control devices are being
nnnnreplaced by the electronic sensor TPL210, used to
nnnnmonitor:
nnnn• Pressure
nnnn• Oil Level
nnnn• Oil Temperature
nnnnThe NT210 unit allows to read and monitor the parameters acquired, generating
nnnnalarms and trip in case of overrun of critical thresholds.
nnnnTPL210
nnnnTECHNICAL SPECIFICATION
nnnnNT210
nnnnPOWER SUPPLY POWER SUPPLY
nnnnDirect connection with the Power-link source of NT210 monitoring Rated values: 24-240 Vac-dc
nnnnunit (9VDC 100mA max) Vdc with reversible polarities
nnnnDATA MEASURED
nnnnOil temperature from -40 to +200°C
nnnnResolution: ±1°C
nnnnAccuracy: ±1°C full scale value
nnnnOil pressure: from 0 to 500 mBar
nnnnResolution: ±10 mBar ±10 digit
nnnnAccuracy: ±2% full scale value
nnnnLevel: level reading represents the oil centimetres introduced in
nnnnthe measuring rod, with accuracy ±1cm
nnnnDIMENSIONS
nnnnExternal housing dimensions: DIN B head
nnnnStainless steel rod length = 166 mm
nnnn3/4"GAS sliding union
nnnnINPUTS
nnnnDigital input for connection with TPL210 sensor
nnnnOUTPUTS
nnnn2 alarm relays (AL1-AL2)
nnnn1 relay to manage ventilation (FAN)
nnnn1 relay for sensor fault or working anomaly (FAULT)
nnnnOutput relays with 5A-250 Vac coscp=1
nnnnPower-link output (9Vdc 100 mA max.) to feed TPL210
nnnnsensor.
nnnnwww.tecsystem.it
nnnnCONTACTS:
nnnnVia Leonardo da Vinci, 54/56
nnnn20094 Corsico (Ml)-ITALY
nnnnTel.:+39 02 48 60 10 11
nnnnFax: +39 02 48 60 07 83
"