BARRA series0 pages
TRAFOFAN :
nnnntransformer cooling system *
nnnnELENCO MODELLI BARRE Dl VENTILAZIONE - FAN COOLING SYSTEM BARRAS
nnnnMod. Barra Portata (m3/h) singola Barra Potenza Trafo ipotizzata Ingombro Barra
nnnnBarra mod. Air flow (m3/h) each Barra Hypothetical transfo power Barra dimensions
nnnnBarra 400
nnnn540
nnnnda/from 100 a/to 315 KVA
nnnn10 mm
nnnnInterasse ventilatori
nnnnDistance between center fans
nnnn520-670 mm
nnnnModello ventilatori
nnnnFans model
nnnnTTG240x3
nnnn615
nnnnda/from 400 a/to 630 KVA
nnnn1460 mm
nnnn670-1060 mm
nnnnTTG300x3
nnnnBarra 1200
nnnn1200
nnnnda/from 800 a/to 1250 KVA 1400 mm
nnnn470-585 mm
nnnnTG-180x3
nnnnda/from 1600 a/to 2000 KVA 1800 mm
nnnn470-700 mm
nnnnTG360x3
nnnnBarra 3600
nnnn3600
nnnnda/from 2500 KVA
nnnn2300 mm
nnnn670-770 mm
nnnnTG500x3
nnnnCARATTERISTICHE TECNICHE DEI VENTILATORI - CROSS FLOW FAN TECHNICAL SPECIFICATIONS
nnnnBarra di riferimento - Ref. 400 600 1200 1800 3600
nnnnMotore / Motor TG240 monofase TG300 monofase TGI 80 monofase TG360 monofase TG500 monofase
nnnnTens.nominale* / N.V. 230VAC±10°/o 230VAC±10°/o 230VAC±10°/o 230VAC±10°/o 230VAC±10°/o
nnnnFrequenza* / Hz 50 Hz 50 Hz 50 Hz 50 Hz 50 Hz
nnnnPot. assorbita / P. absorbed 38 W 40 W 95W 95W 95W
nnnnNum.del poll / N° poles 2 2 2 2 2
nnnnAmps, assorbiti / Absorbed 0;35A 0;37A 0;50A 0;50A 0;50A
nnnnClasse di isolamento
nnnnF F B B B
nnnnClass of insulation
nnnnIP 00 00 40 40 40
nnnn*Alimentazioni speciali disponibili su richiesta / Special power supply available under request.
nnnnwww.tecsvstem.it
"