6654030 pages
TEMPERATURE
Product Data Sheet
DS3107
Smart PT-100 Temp Transmitter
INTRODUCTION: GEN206/P
SPECIFICATION @ 20oC
The GEN206/P is a cost effective “smart” in-head
transmitter that accepts PT100 temperature sensors
and converts sensor output over a configured range
to a standard industrial (4 to 20) mA transmission
signal.
Input
PC configuration allows the user to select Range,
units and Burnout direction, without requiring
calibration equipment. Configuration is performed
quickly using our new USB port driven configurator
by simply connecting two clips to the GEN206/P loop
terminals and following the software instructions.
Calibration set up may be saved as a file on the PC for
later use.
Sensor Type
Senor Range
Sensor Connection
Minimum Span (*1)
Linearisation
Pt100 100 R @ 00C 2 or 3 wire
-200 to +850oC [18-390 ohm]
Screw terminal
25oC
BS EN60751 (IEC 751)
standard / JISC 1604
Measurement Accuracy (*2) 0.1oC ±0.05% of reading
Thermal Drift
0.0025% / oC
Excitation Current
<200 µA
Max Lead Resistance
20 ohms/leg
Lead Resistance Effect
0.002oC/ohm
Output
Output Type
Output Range
Output Connection
Max Output
The GEN206/P in-head transmitter incorporates the
latest digital technology to ensure accurate drift free
performance.
Min Output
PC CONFIGURATION
Accuracy
Equipment
Computer
Loop Voltage Effect
Thermal Drift
Max Output Load
USB Configurator
Running WindowsTM XP or
later with USB port
Comprising: USB
configurator, leads,
software downloadable
2 wire 4-20 mA current loop
4-20mA
Screw terminal
21.5 mA (in high burnout
condition)
<3.9 mA (in low burnout
condition)
(mA output / 2000) or 5 µA
(whichever is the greater)
0.2 µA/V
1µA/oC
(Vsupply -10) K ohms
21
eg (700 ohms @ 24V)
Method
Load PC with USB_Link software.
Connect USB Configurator to PC USB port
using cable.
Connect tool clips to GEN206 loop terminals
red (+) black (-).
Run software, set configuration required and
save to device.
DS3107
Page 1 of 2
"