ADiR0 pages
Small Compact Control Systems
Revision: III/08
adir_d_en_101
ADIR
Compact Control System with Display
•
•
•
•
•
•
8 × relay output
6 × universal I/O
DI contact / AI Ni1000 / DO
RS232 (RJ45), according to EIA-561
RS485 with galvanic separation
35 mm DIN rail mounting
Back-lit LCD display, 2 × 8 characters,
membrane keyboard with 6 keys
8
≅V
≅V
1
2
PWR
RUN
1
RS232
G485
B
A
3
4
5
RDO.0
6
7
RDO.1 RDO.2 RDO.3
8
9
10 11
ADIR
ERR
S0
S1
S2
Rx232
Tx232
Rx485
Tx485
26 25 24 23 22 21 20 19 18
AGND IO.5 IO.4 IO.3 GND IO.2 IO.1 IO.0 AGND
17 16 15 14 13 12
RDO.7
RDO.6 RDO.5 RDO.4
TECHNICAL DATA
Universal inputs / outputs
Digital inputs
Analogue inputs
Digital outputs
I/O configuration
Inputs protection
Galvanic separation of inputs / outputs
Relay outputs
Switched power (resistive load)
Switch on time
off time
Contact lifetime
without load / nominal load
Max. switch on frequency
without load / nominal load
Serial communication interface
LCD display
Keyboard
Cover protection rate
Signal connection
Power supply
Power consumption (without outputs)
Operating temperature
Max. ambient humidity
Weight
Dimensions (w × h × d)
Back-up battery lifetime
Programming
6×
Non-potential contact
Ni1000 / 0 to 5 V *) / 0 .. 20 mA *)
15 V DC through 3K92 resistor
by application
Diodes + 820 Ohm resistor
No
8 × normally opened relay 230 V / 2 A AC
500 VA AC / 70 W DC
5 ms
1 ms
30×106 / 1×105 cycles
72000 / 360 hour-1
RS232 (RJ45), according to EIA-561
RS485 with galvanic separation (PA256 VE connectors) #)
2 x 8 characters, back-lit, 4.75 mm height
6 keys
IP20
Screw clamps PA256 VE (5.08 mm)
24 V AC ±20 % or
18 V AC ±20 %
Max. 200 mA at 24 V DC
0 to 50 °C
< 95 % non-condensing
350 g
106 × 95 × 74 mm
5 years
DetStudio
*) Accuracy only 5 %, external resistor is needed for current range
#
) Insulation strength 300 V AC / 1 minute, galvanic separation may not be used for safe and unsafe parts
separation
ORDERING INFORMATION
ADIR
TRF01
Notice:
Compact control system, full connector set, user’s manual, warranty card
Power supply transformer 18 V AC / 5 VA, 35 mm DIN rail mounting
Since 1.3.2008 is ADIR control system supplies only with RS485 interface.
AMiT, spol. s r.o., Naskové 3/1100, 150 00 PRAGUE, Czech Republic
Tel.: +420 222 780 100, +420 222 781 516, Fax: +420 222 782 297
e-mail: amit@amit.cz
Technical support: support@amit.cz
Tel.: +420 549 210 276, +420 549 210 403
www.amit.cz/support