MCOV MICRO-CAM OIL VALVES0 pages
CAPACITIES
MCOV MICRO-CAM OIL VALVES
B SERIES VALVES
The B series Micro-Cam Oil Valve capacities cover the normal range of most industrial combustion applications.
These valves travel from 0 to 180°, i.e., closed to full open, and have a linear flow curve at a constant differential
pressure over the entire flow range. For example, the flow at valve position 18 is two times greater than at valve
position 9.
FULL OPEN VALVE CAPACITY
PIPE
MODEL
NUMBER
NPT
B-1/2-12
PRESSURE DROP (psig)
SIZE
1
5
10
15
20
25
30
35
40
45
OIL CAPACITY (gph) @ 180° VALVE POSITION
50
75
100
1/2
20
44
63
77
141
173
200
B-1/2-16
1/2
30
70
98
116
134
150
164
177
189
201
212
260
300
B-1/2-18
1/2
38
89
120
147
170
190
207
224
239
255
268
329
380
B-1/2-20
1/2
50
116
156
192
222
248
271
292
312
332
349
428
495
B-1/2-24
1/2
67
157
211
260
300
335
366
395
422
449
472
580
670
89
100
110
118
126
134
F,G, & K SERIES VALVES
The F,G, & K series Micro-Cam Oil Valves are high capacity valves with the same basic construction and operating
features as the B series except for minor design variations; 120° travel form closed to full open position to facilitate
automatic control, and a non-linear flow curve at a constant differential pressure over the entire flow range. The nonlinear flow curve indicates that the flow is not directly proportional to the valve position. For example, the flow at
valve position 12 is not necessarily two times greater than at valve position 6.
FULL OPEN VALVE CAPACITY
PIPE
PRESSURE DROP (psig)
MODEL
SIZE
NUMBER
NPT
1
5
10
15
20
25
30
35
40
45
OIL CAPACITY (gph) @ 120° VALVE POSITION
50
75
100
F-1/2-16
1/2
28
62
88
108
124
140
154
165
176
187
197
242
280
F-1/2-18
1/2
49
109
155
189
218
245
269
289
308
328
345
423
490
F-1/2-20
1/2
75
167
237
290
333
375
412
442
472
502
528
648
750
F-1/2-24
1/2
117
261
369
453
520
585
643
690
737
783
824
1012
1170
G-1-29
1
153
342
484
594
682
767
843
905
966
1027
1081
1326
1534
K-1-29
1
182
406
575
705
809
910
1001
1073
1146
1219
1283
1574
1820
K-1-38
1
245
547
774
949
1090
1225
1347
1445
1543
1641
1727
2119
2450
NOTES:
1. Capacities based on No. 2 fuel oil at .849 s.g. and 60°F.
2. Pressure drop across full open valve. Actual test data measured at 25 psig pressure drop, all other capacities calculated.
3. When ordering, specify if valve is to be equipped with hand lever, hand wheel or adjustable radius lever for automatic
control.
(OVER)
In accordance with Hauck’s commitment to Total Quality Improvement, Hauck reserves the right to change the specifications of products without prior notice.
HAUCK MANUFACTURING CO., P.O. Box 90, Lebanon, PA 17042-0090 717-272-3051
Fax: 717-273-9882
5/03
www.hauckburner.com