Capacity expansion through second site in Hochdorf; implementation of a logistics centre
LOADING
Data sheet series SKA0 pages
نسخه متنی
"
Whenever water-cooled circulation is required, cooling
systems and chillers from the SKA series are the ideal solution.
Equipped with an integrated cooling circuit and a
vast cooling capacity range, they are widely used in all industrial
applications, from 1 KW for laboratory processes
through to 1,000 KW in central systems. Premium quality
and process reliability characterise these closed-circuit
and contamination-free systems with a variety of special
customizing options to meet special requirements and
operation conditions.
SKA 1-60
Standard equipment
General
• Rugged, powder-coated sheet steel housing
• High-quality materials and components
• Suitable for indoor operation
• Air-cooled or water-cooled condensers
Hydraulics
• Nominal capacity at 10 °C water temperature
and ambient temperature of 35 °C
• Refrigerant R134a or R404A
Electrical and control equipment
• Micro-processor controller with control accuracy
of up to ± 1K
• Switch box to IP54
• Capacity control from SKA 36
Options
• SC standard controller with colour display
• Equipment for extreme ambient temperatures
• Equipment for extreme fl uid temperatures
of between -50 °C and +180 °C
• Split construction with external condenser
• Pressure gauging
• Flow rate metering by means of differential pressure
• Additional heater for extended temperature range
• Tank pump units
• Connection for various analogue and digital
electric interfaces
• Virtually unlimited hydraulic and electric options
SINGLE Temperiertechnik GmbH, Ostring 17-19, 73269 Hochdorf/Germany
Tel.: +49 (0)7153/3009 - 0, Fax: +49 (0)7153/3009 - 50, www.single-temp.de
SINGLE Cooling systems and chillers with integrated cooling circuit
SKA series