PR5020 pages
PR502
Advanced, Full Featured Profile Controller
Features:
In depth Ramp / Soak Control
Dual Display, 4 digit, 7 segment LED
LED Status Indicator: Relay ON, Tune, Alarm, Manual
4 Front Panel Control buttons
TC / RTD Input, Analog Input
ON/OFF, PID, PIDAutotune
°C/°F Selectable
10 Programs, 16 Steps Each
Alarm at Each Step
Memory Retention
Two Setpoints
Size: 1/16 DIN 48mm x 48mm
Certifications: C C c^JL
Technical Specifications
Display
Digits
LED Indications
Input Specifications
Inputs
Sampling time
Input Filter (FTC)
Resolution
Temperature Unit
Indication Accuracy
Output Specifications
Control
Contact Rating (SPST)
SSR Drive (Voltage Pulse)
Current
Voltage
Alarm
Contact Rating (SPST)
SSR Drive
4 digit 7 Segment LED, Dual display
Height of Upper Display: 0.3785"
Height of Lower Display: 0.2720"
Relay ON, Alarm, Manual mode, Tune
Thermocouple (J,K,T,R,S,C,E,B,N,L,U,W,
Platinel II), RTD (Pt100)
DC Analog Inputs (-5 to 56mV, 0 to 10V,
0 to 20mA)
200 ms
0.2 to 10.0 sec
1/0.1°forTC/RTD only
(Fixed 1° resolution for R & S type TC)
Decimal point position selectable:
1/0.1/0.01/0.001 for analog input
°C/°F Selectable
ForTC inputs: 0.25% of F.S. ±1°
For R & S type TC inputs: 0.5% of F.S. ±2°
(20 min of warm up time for TC inputs)
For RTD inputs: 0.1% of F.S. ±1°
For Analog Input: ±0.5%, ±1 digit
(F.S. = Full Scale)
1
5A @ 230V AC / 30V DC, resistive
18V DC, 20mA
0/4 to 20mA DC
(loop impedence:500O max.)
0to5/10VDC
(load resistance :10KQ min.)
1
5A @ 230V AC / 30V DC, resistive
12V DC (20mA)
Functional Specifications:
Control Action
Proportional Band (P)
Integral Time (I)
Derivative Time (D)
Alarm
Modes
Operation
Hysteresis
Hold / Standby mode
Annuniator
Reset Action
Probe Break Action
Profile
No. of Profiles
No. of Steps
Ramp/Soak Time Range
Target Temperature Range
Other Profile Parameters
1) PID
2) 0N-0FF
0.0 to 400.0"
0 to 3600 sec
0 to 200 sec
Deviation high, Deviation low, Band, Full scale
high, Full scale low, Sensor break
Absolute / Deviation mode
Programmable
Programmable
Programmable
Programmable - Automatic or Latched
Upscale
10
16 each
0.01 to 99.59 Hrs : Min
SPLLtoSPHL
Link profiles, Programmable repeat cycle,
Power down resume / Reset options, Deviation
hold, Alarm at each step with settable alarm
duration
Supply Voltage
Supply Voltage
Power Consumption
85 to 270V AC/DC (50/60Hz)
Optional -24V AC/DC, ±10%
6VAmax@230VAC
Environmental Specifications
Temperature
Humidity (non-condensing)
Weight
Protection Level
Operating: 0 to 50°C (32 to 122°F)
Storage:-20 to 75°C (-4 to 167T)
95% RH
170 gms
IP65 for faceplate
www.selec.com
"