600DT0 pages
600DT
17.5mm DIN Rail Timer
Features:
• 15 Functions
• 8 Time Ranges
• Front Key Pad Setting
• Universal supply voltage
• Slim, Space Saving Design
• DIN Rail Mount
Size: DIN 17.5mm
Certifications: C€ 'H"
Technical Specifications
Input Specifications
Accuracy
Reset
Output Specifications
Output Contact
Contact Rating
Functional Specifications
Modes
Time Ranges
Counting Direction
Memory
Supply Voltage
Supply Voltage
Power Consumption
Setting: ± 0.1 % of set time or ±50msec
(whichever is greater)
For Y contact operation: +100msec
Repeat: ± 0.1 %
Front Key, On interruption of power;
Reset time < 100 msec
SPDT (1 C/O)
8A@250VAC
On delay (A)
Interval (B)
Asymmetrical cyclic OFF first (C)
Asymmetrical cyclic ON first (D)
Cyclic equal OFF first (E)
Cyclic equal ON first (F)
Pulse output (H)
Delay on break (J)
Delay on make / break (K)
Interval after break (L)
Single shot (P)
Retriggerable Single shot (Q)
Latching relay (R)
Delay with Totalise (t)
Interval with Totalise (U)
0-99.9 sec/min/hr
0-999 sec/min/hr
0 - 9:59 min:sec
0-9:59hr:min
Down
Yes (selectable)
20-240VAC/DC(AC:50/60 Hz)
4VAmax
Environmental Specifications
Temperature
Humidity (non-condensing)
Weight
Protection Level
Operating: 0 to 50°C (32 to 122°F)
Storage: -20to75°C (-4to167°F)
95% RH
69gms (0.163 lbs)
IP40 for Casing
IP20 for terminals
Dimensions
o
o
o
o
o
o
o
o
17.5
mm
Symmetrical 35mm Din Rail (EN50022) Mouting
Terminal Connections
44mm
60mm
A1 | A2 |
□ | |
15 | 25 |
16 | 18 |
0 I Control
O | Contact Y1
NCL^JNO
COM
Cable Size (AWG): 16; Tightening Torque (Lb-inch): 5.3....7.08 ibf.in
Cable Size (mm2): 1.5; Tightening Torque (N-m): 0.6....0.8 N. M
Ordering Information
Supply Voltage | Certification | ||
utrawn IND.CONT.EQ. | |||
600DT | 20-240V AC/DC | ■ | |
600DT-CU | 20-240V AC/DC | ■ | ■ |
www.selec.com
"