Process Cooling Application - ENR CB biogas application0 pages
cool i with
HITEiVIA
international
Aircooled liquid chillers ENR-CB series for biogas application, scroll compressors, brased plate evaporator, condenser with copper tubes and aluminium finned core and axial fans, RV "fan speed cut-phase regulator" included, RC "crankease heater" included | |||||||
Process Cooling Application Model 004 | 005 | 008 | 010 | 012 | 016 | 018 | 022 |
NOMINAL COOLING CAPACITY (1) kW 4,6 | 5,3 | 7,9 | 10,2 | 12,2 | 15,8 | 18,0 | 22,5 |
NOMINAL COOLING CAPACITY (1) Frig/h 3956 | 4558 | 6794 | 8772 | 10492 | 13588 | 15480 | 19350 |
TOTAL COMPRESSORS NOMINAL ABSORBED POWER (1) kW 1,7 | 1,7 | 2,6 | 3,4 | 3,9 | 5,2 | 5,8 | 6,7 |
COP kW/kW 2,74 | 3,10 | 2,99 | 2,98 | 3,10 | 3,05 | 3,08 | 3,35 |
EER kW/kW 2,58 | 2,92 | 2,74 | 2,78 | 2,75 | 2,79 | 2,76 | 2,99 |
ESEER 3,4 | 3,3 | 3,3 | 3,6 | 3,8 | 3,9 | 3,9 | 3,8 |
IPLV 3,9 | 4,1 | 4,1 | 4,1 | 4,3 | 4,3 | 4,3 | 4,5 |
COMPRESSORS nr. 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 |
REFRIGERATING CIRCUITS nr. 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 |
PARTION STEP nr. 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 |
REFRIGERANT | R410A | ||||||
HYDRAULIC SECTION | |||||||
NOMINAL WATER FLOW m3/h 0,8 | 0,9 | 1,4 | 1,8 | 2,1 | 2,7 | 3,1 | 3,9 |
EVAPORATOR PRESSURE DROP kPa 41 | 55 | 48 | 52 | 52 | 60 | 66 | 71 |
AVAILABLE PRESSURE mca 10 | 9 | 16 | 15 | 14 | 12 | 11 | 11 |
MAXIMUM PUMP ABSORBED POWER kW 0,25 | 0,25 | 0,62 | 0,62 | 0,62 | 0,62 | 0,62 | 0,76 |
MAXIMUM PUMP ABSORBED CURRENT A 1,9 | 1,9 | 1,35 | 1,35 | 1,35 | 1,35 | 1,35 | 1,48 |
HYDRAULIC CONNECTIONS BSP/DN 1/2" | 3/4" | 1" | 1" | 1" | 1" | 1" | 1" |
TANKVOLUME dm3 40 | 40 | 50 | 50 | 50 | 50 | 110 | 110 |
FAN SECTION (AXIAL) | |||||||
TOTAL AIR FLOW m3/h 1200 | 1500 | 4100 | 4100 | 4750 | 4750 | 6500 | 7400 |
FANS nr. 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 |
FANS ABSORBED POWER kW 0,10 | 0,10 | 0,25 | 0,25 | 0,49 | 0,49 | 0,68 | 0,81 |
FANS ABSORBED CURRENT A 0,52 | 0,52 | 1,10 | 1,10 | 2,36 | 2,36 | 3,00 | 1,54 |
TOTAL ELECTRIC DATA | |||||||
NOMINAL ABSORBED POWER kW 2,0 | 2,1 | 3,5 | 4,3 | 5,1 | 6,3 | 7,1 | 8,3 |
MAXIMUM ABSORBED CURRENT(F.LA) A 9,4 | 11,2 | 9,8 | 10,1 | 12,9 | 13,5 | 18,4 | 18,9 |
MAXIMUM PEAK CURRENT (L.R.A.) A 38,9 | 44,9 | 49,4 | 49,4 | 70,4 | 70,4 | 74,4 | 103,5 |
ELECTRIC FEED V/Ph/Hz 230/1/50 | 400/3/50N | ||||||
NOISE DATA | |||||||
SOUND PRESSURE (2) dB(A) 51,6 | 51,5 51,4 | 51,4 | 52,2 | 52,2 | 53,3 | 55,5 | |
DIMENSIONS AND WEIGHT | |||||||
LENGTH mm 600 | 600 | 820 | 820 | 820 | 820 | 1010 | 1010 |
WIDTH mm 655 | 655 | 615 | 615 | 615 | 615 | 720 | 720 |
HEIGHT mm 1035 | 1035 | 1360 | 1360 | 1360 | 1360 | 1580 | 1580 |
WEIGHT EMPTY kg 90 | 102 | 175 | 180 | 185 | 190 | 230 | 260 |
WEIGHT OPERATIVE kg 130 | 145 | 225 | 230 | 235 | 240 | 360 | 390 |
The manufacturer reserves the right to modify specifications without notice. Updated on 29/08/2014
Data referred to:
(1) Inlet/Outlet water temperature = +12/+7 °C - Condenser air temperature = +35°C; fouling factor = 0.000043 rrfK/W
(2) Sound pressure level referred to measures according to normative IS03744, pressure level at distance of 10 m, referred to free field on reflecting surface
"