Cooling Big Evolution chillers - EET series0 pages
Aircooled liquid chillers EET series, screw compressors R134a, shell and tube evaporator, brazed-plate economizers, condenser with copper tubes and aluminium finned core and axial fans
Cooling Big Evolution
Model
210
250
300
330
380
430
510
580
650
700
750
800
920
1000
1100
1210
1350
NOMINAL COOLING CAPACITY (1)
kW
223
252
311
335
399
444
534
609
670
723
758
824
946
1035
1124
1277
1410
1500
1589
TOTAL COMPRESSORS NOMINAL ABSORBED POWER (1)
kW
70,6
75,0
97,6
102,4
114,0
134,8
168,8
189,0
195,0
214,0
231,4
232,2
263,6
290,8
314,4
379,8
452,6
474,4
COP (1)
kW/kW
3,16
3,36
3,19
3,27
3,50
3,29
3,16
3,22
3,44
3,38
3,28
3,55
3,59
3,56
3,58
3,36
3,12
3,35
EER (1)
kW/kW
2,85
3,04
2,85
2,94
3,18
2,95
2,90
2,98
3,13
3,10
3,02
3,23
3,21
3,22
3,25
3,08
2,87
3,07
ESEER
4,08
4,25
4,28
4,25
4,25
4,37
4,23
4,26
4,35
4,25
4,27
4,47
4,45
4,30
4,38
4,30
4,29
4,32
IPLV
4,69
4,80
4,82
4,80
4,82
5,00
4,82
4,86
4,86
4,82
4,87
5,13
5,07
4,86
5,00
4,86
4,84
4,89
COMPRESSORS
nr.
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
REFRIGERATING CIRCUITS
nr.
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
PARTITION STEPS
%
0-33-66-100
NOMINAL WATER FLOW
m3/h
38,4
43,4
53,6
57,7
68,7
76,5
92,0
104,9
115,4
124,5
130,6
141,9
163,0
178,3
193,6
220,0
242,9
273,7
EVAPORATOR PRESSURE DROP
kPa
42
40
40
44
57
61
43
61
67
72
76
59
65
71
70
69
76
82
AVAILABLE PRESSURE (2)
mca
24,5
24,5
28,4
24,5
22,9
25,4
25,0
24,0
23,3
26,8
25,9
26,6
27,0
24,9
28,4
25,6
23,9
19,4
PUMP MOTOR NOMINAL POWER (2)
kW
5,5
5,5
7,5
7,5
7,5
11,0
11,0
15,0
15,0
18,5
18,5
18,5
22,0
22,0
30,0
30,0
30,0
30,0
HYDRAULIC CONNECTIONS (VICTAULIC)
DN
125
125
125
125
125
150
150
150
150
150
200
200
200
200
200
200
200
200
TANK VOLUME (2)
dm3
450
450
600
600
600
600
600
600
600
600
600
800
800
800
800
800
1000
1000
396000
0-25-50-75-100
HYDRAULIC SECTION
FAN SECTION (AXIAL)
m³/h
76000
72000
126000
111000
108000
168000
156000
152000
180000
185000
183000
222000
308000
304000
296000
333000
360000
FANS
nr.
4
4
6
6
6
8
8
8
10
10
10
12
16
16
16
18
20
22
FANS ABSORBED POWER
KW
7,76
7,76
11,64
11,64
11,64
15,52
15,52
15,52
19,40
19,40
19,40
23,28
31,04
31,04
31,04
34,92
38,80
42,68
A
15,60
15,60
23,40
23,40
23,40
31,20
31,20
31,20
39,00
39,00
39,00
46,80
62,40
62,40
62,40
70,20
78,00
85,80
TOTAL AIR FLOW
FANS ABSORBED CURRENT
TOTAL ELECTRIC DATA
MAXIMUM ASSORBED CURRENT PER COMPRESSOR (F.L.A.)
A
115
122
146
163
183
209
254
294
319
319
358
374
430
473
508
589
580
637
MAXIMUM PEAK CURRENT PER COMPRESSOR (PW) (L.R.A.)
A
239-450
239-450
329-530
423-650
497-765
640-985
646-950
915-1345
996-1465
996-1465
996-1465
527-1580
693-2080
777-2330
827-2480
915-2745
935-2805
935-2805
PW
PW
PW
PW
PW
PW
PW
PW
PW
PW
PW
Y-D
Y-D
Y-D
Y-D
Y-D
Y-D
Y-D
MOTOR CONNECTION (PW = part winding; Y-D = star-delta)
ELECTRIC FEED
400/3/50
V/Ph/Hz
NOISE DATA
dB(A)
64,2
64,4
63,7
64,0
64,5
65,3
67,8
69,8
70,1
71,0
71,2
71,5
71,7
72,3
73,1
73,5
74,7
74,9
LENGTH
mm
3100
3100
4050
4050
4050
5000
5000
5000
5950
5950
5950
6900
8800
8800
8800
9750
10700
11650
WIDTH
mm
2210
2210
2210
2210
2210
2210
2210
2210
2210
2210
2210
2210
2210
2210
2210
2210
2210
2210
HEIGHT
mm
2450
2450
2450
2450
2450
2450
2450
2450
2450
2450
2450
2450
2450
2450
2450
2450
2450
2450
WEIGHT EMPTY
kg
3000
3150
3900
4200
4300
4600
4700
4900
5600
5850
6000
6500
8300
8400
8500
9400
10400
11300
WEIGHT OPERATIVE
kg
3150
3300
4060
4370
4480
4780
4890
5100
5820
6100
6290
6790
8620
8750
8850
9750
10780
11690
SOUND PRESSURE (3)
DIMENSIONS AND WEIGHT
The manufacturer reserves the right to modify specifications without notice.
Data referred to:
(1) 100% of Load - Inlet/Outlet water temperature = +12/+7 °C - Condenser air temperature = +35°C; fouling factor = 0.000043 m²K/W.
(2) With options NT.WP (no tank - water pump) or T.WP (tank - water pump).
(3) Sound pressure level referred to measures according to normative ISO3744, pressure level at distance of 10 m, referred to free field on reflecting surface
updated on 08/04/2015
"