ICG 653/UNIVERSAL Cable glands0 pages
Cable Glands
ICG 653/UNIVERSAL
Hazardous Area
88
Flameproof Exd & Increased Safety Exe & Restricted
Dual Certified ATEX / IECEx
15.0mm
Inspectable
Compound
Deluge Boot
• Outdoor or indoor use.
• For use with single wire armour ‘W’, wire braid ‘X’, steel tape armour ‘Z’,
elastomer and plastic insulated cables.
• For particular use with:-
Armour/Braid 'C'
- Cables that are not effectively filled, compact and/or circular,
Ø 'B'
Ø 'E'
Ø 'D'
Entry Thread
Metric
Entry
Application
'G' Approx (Fully Compressed Length)
have tape bedding or have hygroscopic fillers.
- Cables that exhibit ‘Cold Flow’ characteristics.
- Enclosures containing an ignition source in gas group IIC
areas or containing an ignition source in a Zone 1 area.
• See technical section for installation rules and regulations.
CABLE GLAND SELECTION TABLE
Entry Thread Size
Size Metric
Ref.
Os
O
A
B
C
C2
D
E
F
M20
M20
M20
M25
M32
M40
M50
M63
M75
NPT *
Standard
or Option
½"
½"
¾" or ½"
1" or ¾"
1¼" or 1"
1½" or 1¼"
2" or 1½"
2½" or 2"
3" or 2½"
Hexagon
Dimensions
Cable Acceptance Details
Inner Sheath / Cores
Armour / Braid ‘C’
Max. Over Max Inner Max. No. of Outer Sheath ‘B’
Cores ‘D’
Sheath ‘E’
Cores
Min
Max Orientation 1 Orientation 2
8.9
10.0
6
5.5
12.0
0.8 / 1.25
0.0 / 0.8
8.9
10.0
6
9.5
16.0
0.8 / 1.25
0.0 / 0.8
11.0
12.5
10
12.5
20.5
0.8 / 1.25
0.0 / 0.8
16.2
18.4
21
16.9
26.0
1.25 / 1.6
0.0 / 0.7
21.9
24.7
42
22.0
33.0
1.6 / 2.0
0.0 / 0.7
26.3
29.7
60
28.0
41.0
1.6 / 2.0
0.0 / 0.7
37.1
41.7
80
36.0
52.6
1.8 / 2.5
0.0 / 1.0
47.8
53.5
100
46.0
65.3
1.8 / 2.5
0.0 / 1.0
59.0
66.2 / 65.3¹
120
57.0
78.0
1.8 / /2.5
0.0 / 1.0
'G'
Across
Flats
Across
Corners
24.0
24.0
30.0
36.0
46.0
55.0
65.0
80.0
95.0
26.5
26.5
32.5
39.5
50.5
60.6
70.8
88.0
104.0
67.0
67.0
67.0
73.6
78.0
82.4
88.7
92.7
99.4
All dimensions in millimetres (except * where dimensions are in inches). Metric entry threads are 1.5mm pitch as standard, 15mm length of thread.
¹ Smaller value is applicable when selecting reduced NPT entry option. Note: Larger sizes are available.
Technical Data
• Flameproof Exd and Increased Safety Exe II 2 GD ExtD A21.
• Certificate No’s: Baseefa06ATEX0058X and IECEx BAS 06.0015X.
• Suitable for use in Zone 1, Zone 2, Zone 21, Zone 22 and in
Gas Groups IIA, IIB and IIC.
• Construction and Test Standards: IEC/EN 60079-0, IEC/EN 60079-1,
IEC/EN 60079-7, IEC/EN 61241-0 and IEC/EN 61241-1.
• Ingress Protection: IP66, IP67 and IP 68 (30 metres for 7 days) to
IEC/EN 60529 and NEMA 4X.
• Deluge Protection to DTS01.
• Operating Temperature Range: -60°C to +80°C.
• Assembly Instruction Sheet: AI 301.
• Alternative certification options available:
Exe II
BR-Exd IIC / Exe II
Exd IIC / Exe II
GOST R-Exe IIU
GOST K- Approved for use in Kazakhstan
DNV Marine Approval
ABS Marine Approval
Features
• Provides a barrier seal to the individual insulated cores within the cable
and prevents entry of the products of an explosion into the cable.
• Assembly of the cable gland compresses and distributes the compound
evenly to create a barrier seal at the point of entry into the enclosure.
• The compound chamber may be separated from the cured compound
•
•
•
•
•
to ensure that the chamber has been effectively filled. If required,
external voids can be repaired.
Provides armour clamping, using one clamping arrangement for
all armour / braid types.
Provides an outer deluge seal to prevent moisture ingress to the
cable armour / braid.
Provides a cable retention and low smoke and fume, zero halogen seal
onto the cables outer sheath.
Manufactured in Brass (standard), Nickel Plated Brass,
316 Stainless Steel or Aluminium.
Brass NPT entries are nickel plated as standard.
Alternative Reversible Armour Clamping Rings (RAC)
Size Ref.
B
C
C2
D
E
F
SELECTION TABLE
Steel Wire Armour / Braid / Tape
Orientation 1
Orientation 2
0.9 - 1.25
0.5 - 0.9
1.2 - 1.6
0.6 - 1.2
1.2 - 1.6
0.6 - 1.2
1.45 - 1.8
1.0 - 1.45
1.45 - 1.8
1.0 - 1.45
1.45 - 1.8
1.0 - 1.45
Ordering Information
Format for ordering is as follows: Alternative Clamping Ring (AR), add suffix AR to ordering information.
Cable Gland Type
ICG 653/UNIV
Size
C
Thread
M32
(OPTIONAL)
AR
Cable Gland Type
ICG 653/UNIV
Size
C
Thread
1 1⁄4"NPT
(OPTIONAL)
AR
Two part sealing compound and assembly instructions are supplied with the cable gland.
Connection Solutions
www.ehawke.com
HPG01
UPD 090610