61F-GPN-BT / -BC0 pages
Conductive Level Controller
61F-GPN-BT/-BC
CSM_61F-GPN-BT_BC_DS_E_5_2
Battery (24 VDC) allows use in locations
without AC power supply. AC sine-wave
voltage between electrodes enables stable
detection with no electric corrosion.
• Outputs can be set to self-hold at ON or OFF using special circuits.
• Adjustable sensitivity, with an operating resistance range of 0 to
100 kΩ, allows use for a wide variety of liquids.
• Relay contact chattering conventionally caused by waves eliminated using open collector output, reducing contact wear.
• Meets CE marking and is a UL recognized component.
Refer to Safety Precautions for Floatless Level
Controllers.
Features
The 61F can now run on DC power to allow energy savings, greater safety, and use in
emergency situations.
Combines DC Power
Supply with AC Sensing
Method
AC sine-wave signals are
sent to electrodes using a
built-in DC-AC converter,
preventing electric
corrosion and ensuring
safety.
Supports Multi-channel
Sensing
Power supply circuits and
detection circuits are
isolated, allowing more
than one Controller to be
used in the same tank.
Open Collector Output
Signals can be used as
direct input for a PLC.
PNP output is also
possible using the
connection method.
Oscillator
circuit
Detector
circuit
Upper limit
Mid-point
Control output
is possible for
upper limit,
mid-point, and
lower limit.
Lower limit
Same Wiring for Supply
and Drainage
Supply control and
drainage control can be
performed with the same
wiring (short terminals 7
and 8 for supply control).
This makes it easy to
perform wiring and
confirm connection.
Chattering
Load
Drainage
control
Supply
control
Short-circuit
Valve
Pump
Ordering Information
Product name
Conductive Level Controller
Model number
61F-GPN-BT 24VDC
61F-GPN-BC 24VDC
Open collector (NPN)
Relay contact (SPST-NO)
Front Socket
PF113A-E
Electrode Holder
(See note.)
Note: A variety of Holders are available to suit different types of application. For details, refer to 61F Floatless Level Controller
(F030-E1-8).