D 2011Li0 pages
D 2011Li
for generator sets
12 - 29 kW|15 - 39 hp at 1500 min-1|rpm
EU Stage IIIA
Oil-cooled 2, 3 and 4-cylinder aspirated
Minimised running costs due to low
engine in inline construction with integrated cooling system.
maintenance need and little wear.
Low fuel consumption due to optimised
Direct injection with single injection
combustion.
pumps and optional electronic governor.
Long oil change intervals of up to 1000
hours.
High reliability combined with durability.
A very good load response ensures an
No corrosion or cavitation due to oil
cooling and lubrication.
immediate power supply.
Technical data
Engine type
No. of cylinders
Bore/stroke
Displacement
Weight (incl. cooler and fan)
Governing standard1)
mm | in
l | cu in
kg | lb
D 2011L02i
2
94/112 | 3.7/4.4
1.6 | 95
212 | 467
G2
D 2011L03i
3
94/112 | 3.7/4.4
2.3 | 142
254 | 560
G2
D 2011L04i
4
94/112 | 3.7/4.4
3.1 | 190
293 | 646
G2
D 2011L02i
11.5 | 15.4
12.1 | 16.2
12.7 | 17.0
0.1 | 0.1
13
13
14
D 2011L03i
18.1 | 24.3
19.1 | 25.6
20.1 | 27.0
0.1 | 0.1
20
21
22
D 2011L04i
26.4 | 35.4
27.8 | 37.3
29.2 | 39.2
0.2 | 0.2
30
31
33
50 Hz / 1500 min-1
Power
Continuous Power (COP)2)
Prime Power (PRP)3)
Limited Time Power (LTP)4)
Fan power consumption
Typical Generator Output COP5)
Typical Generator Output PRP5)
Typical Generator Output LTP5)
1)
2)
3)
4)
5)
kW | hp
kW | hp
kW | hp
kW | hp
kVA
kVA
kVA
According to ISO 8528-5.
Continuous Power: No time limitation, plus 10% additional power for governing purpose only.
Prime Power: Average power output ≤ 80%, no time limitation, plus 5% additional power for governing purpose only.
Limited Time Running Power: For up to 500 h/year, thereof a maximum of 300 h/year continuous running.
In consideration of a generator efficiency level of 89 - 90 % and a power factor of 0.8.
The data on this data sheet are for information purposes only and are not binding values. The data in the quotation is definitive.
"