Terminal Head with LED Display0 pages
Data sheet
PT100 LED
DISPLAY
Date
Page
11/2012
1 of 1
TERMINAL HEAD WITH LED DISPLAY
FOR MODEL RT100 / RT200
TERMINAL HEAD LED DISPLAY AND TRANSMITTER
LED DISPLAY TECHNICAL
Input signal: 4-20mA on 2 wires
Power supply for display: self powered on 4-20mA / 24Vdc
Voltage drop: 3.3V at 4 mA, 3.7V at 20 mA
Display: LED 4 digits
Measuring range: from 4 to 20 mA
Max. voltage drop out: 3,7 V
Display LED: 4 digits, height 9.5mm
Indication limits: from -1999 to 9999
Unit: ºC, ºF, ºK, % in cycle: 4sec. value – 2sec. unit
Accuracy: 0.1% range and +/-1digit
Operating ambient temperature: -20 / +70 Deg C
ATEX option available.