C2404B0 pages
OMNITERM TFX SPECIAL FUNCTION MODULE
Model C2404B 24Vdc powered Special Function Module with isolated output.
DATASHEET
• Select from a wide range of computation
functions
• Fully configurable by the user
• Accepts two 4-20mA or 1-10Vdc inputs
• One universal 0-20mA / 0-±10V / 0-±10mA or
pulse output
• Output isolation to 1500Vac
• Output overload detection
• 24Vdc powered
Features
•
•
Select from a wide range of functions:
Average, Deviation, Difference, Multiplication, Ratio,
Minimum, Maximum, Track and Hold, Peak, Valley,
Rate of Change, Ramp Limited, Log etc.
•
1500Vac Isolated Analogue Output
•
Output overload Indicator
•
•
User friendl y configuration software
Wide operating temperature range
•
DIN Rail or surface mountable
•
Narrow 22.5mm module width
•
Designed to meet IEC 61508 SIL1 criteria.
OVERVIEW
The OMNITERM TFX Special Function Module is ideal
for those special applications where mathematical
computations are required on your analogue signals. The
TFX accepts two 1-5V (up to 1-10V) or 4-20mA inputs
and provides one universal output.
The output can be configured for unipolar or bipolar
outputs of current or voltage from ±1mA to ±10mA; 0
20mA; or ± 1V to ±10V, as well as pulse outputs for
totaliser and frequency translation applications.
as belt slip monitoring, dual-redundant analogue inputs,
ratio monitoring, rate -of-change monitoring etc. etc..
This module uses advanced state -o f-the-art digital
measurement techniques, combined with extremely user
friendly software configurability for best ease of use
without factory required setup when ordering .
HIGH RELIABILITY
Full output isolation to 1500Vac ensures trouble-free
installations .
MATHEMATICAL FUNCTIONS
The Omniterm TFX comes equipped with a wide
selection of common mathematical functions . When
combined with the user configurable 32 point linearisation
table, this powerful computation module can be used to
solve a wide range of signal processing applications such
LOW LIFE CYCLE COSTS
The OMNITERM TFX provides extremely low life-cycle
costs by reducing spares stock-holding requirements,
and reducing specialist technical expertise required for
field support, module replacement and field configuration.
This new holistic approach to instrumentation asset
management ensures reliable performance and minimal
down-time.
This product has been designed with high reliability
applications in mind. The output stage has built-in
overload indication to detect overloaded output circuits –
eg. from a wire break or excess resistance when
configured as a current loop, or too low a load resistance
when configured as a voltage output.
This product has been designed to meet the criteria of
IEC61508 for SIL1 applications.
Copyright Omniflex ♦ Subject to change without notice
Datasheet DSC2404BR08 sheet 1 of 4
http://www.omniflex.com
®