Ammonia Gas Detector, NH30 pages
MIL-RAM TECHNOLOGY
no false alarms SlYiCe 199 O ISO 9001:2008 Registered
Tel: 510-656-2001 • Toll-Free: 888-464-5726 • Email: sls@mil-ram.com • Web: mil-ram.com
Model TA-2100 smarter
Ammonia NH3 Gas Detector
Features
Part No. 01-2611
Options
- Modbus RTU
- Relay Module
- Sensor Cable
- Sample Pump
- Duct Mount Kit
- Dust Guard
- Splash Guard
- Wireless Module
-110/220 VAC
- Calibration Kits
- 316 SS Enclosure
no false alarms patented electrochemical sensor technology
Self-Calibration adjusts monthly based on sensor life curve
Auto-Gas Calibration, non-intrusive, hands-free, magnetic switches
Not affected by temperature -4o°C to +5o°C, stable by design
LCD display -12 characters x 2 lines - provides user interface with
magnetic switches - no dip switches - LED alarm indicators
Offsite sensor calibration with memory chip embedded in sensor
Peak Value, 15-min. TWA, Remaining Sensor Life, Replace Sensor
indication and number of days since last gas calibration
Optional Relay Module; low, mid, high and fault conditions
Optional RS-485 Modbus RTU Network interface
Available suitable for use in SIL 2 environments / Advanced diagnostics
Specifications
Applications
Detection Principle:
Detection Method:
Detection Range:
Calibration Method:
Operating Voltage:
Power Requirements:
Electrical Connections:
Cable Requirements:
Optional Connections:
Resolution:
Zero Drift:
Temperature Range:
Humidity Range:
Response Time:
Recovery Time:
Sensor Service Life:
Electronic Enclosure:
Certifications:
Electrochemical - Amperometric
Diffusion or Sample Drawing
o - 200 ppm (parts-per-million)
Non-intrusive, magnetic tool
12 - 30 VDC, 24 VDC nominal
1.08 W @ 24 VDC
Power (24 VDC) and Signal (4-2omA)
3 or 4 wires, shielded
RS-485 Half-duplex (Modbus RTU)
1 ppm minimum detection level
less than 5 ppm
-4o°C to +5o°C
10 - 95% RH, non-condensing
<6o sec. to 90% of final reading
<2 min. to 90% recovery
>2 years typical; normal conditions
Ex-Proof, alum, or 316 SS, Nema 4X
CSA, Class I GR B,C,D haz. loc. avail.
Water Treatment
Wastewater Treatment
Refrigeration
Chemical Processing
Pulp & Paper
Food & Beverage
Laboratories
Metal Treatment
Specifications subject to change without notice
due to continued program of product
innovation.
Toxic • LEL Combustible • Oxygen • VOCs • Hydrides • Hydrocarbons
Gas Detection no false alarms Fire Detection
Tel: 510-656-2001 • Fax:510-656-2004 • Email: sls@mil-ram.com •
"