eStat10 DUO
Electronic Room Hygro-Thermostat
1 switching output each for temperature
and humidity
•t Easy to install
• t2 potential-free switching outputs configurable as
t opener or closer
•t Setpoint and switching hystereses for temperature
t and relative humidity independently configurable
•t Display of current relay switching states
•t 2 continuous 0...10 V signal outputs for relative
t humidity and temperature
•t Temperature compensation
•t Alternating display of relative humidity and temperature
Technical Data
Temperature
Humidity
Measuring range
0...100 %rh
Control range of the temperature
-25...+55 °C
Control range of the relative humidity
5...95 %rh
Setting range of the switching hystereses
Setting range of the switching hystereses
0.5...9 %rh
Output rangest
Measuring uncertainty
t 10...90 %rh at 25 °C max
t 0...10 %rh and 90...100 %rh
t at 25 °C
t Long term stability
t Hysteresis
t Typ. temperature influence
t at 25 °C
≤ ±3 %rh
additional
≤ ±0.2 %rh / %rh
≤ 0.5 %rh/a
≤ ±1 %rh
±0.05 %rh/K
Switching outputs:
2 relay contacts
potential-free, normally open
Setting as opener / closer
Via DIP switch
Switching voltagett
≤ 48V DC / AC
tttt ≥ 100 µV
Breaking capacitytt
Switching cycles (at Pmax)tt
Switching currentttt
≤ 2A
0...10 V DC
0...10 V DC
15...30 V DC
13...26 V AC
Consumption t
≤ 30 mA
www.galltec-mela.de
Operating temperature tt
-30...+60 °C
Storage temperature
-40...+85 °C
Electrical connections at mains terminals
t Wire cross-section at each connectiont
max. 1.5 mm²
max. 1 x Ø 6.5 mm
or 2 x Ø 4.5 mm
Concealed cable
See: User instructions on page 4
Supply voltage
Standards applied
Air, non-pressurised, non-t
condensing, non-aggressive
> 0.9
> 105
typ. ±0.3 K
General Data
Cable diameter
Surface-mounted cablet
≤ 60 W / 62.5 VA
Power factortttt
Continuous output rel. humidityt
Continuous output temperature
Measuring uncertainty
at 23°C and ≤ mA switching current
Measuring medium
t
Electrical data
0.1...10 K
0...+50 °C
-30...+70 °C
0...+100 °C
Further ranges on demand
EN 61326-1
Housing IP rating
Safety category
Housing materials
Housing colour ttt
Digital dispaly
IP 30D
III
ABS
similar to RAL 9003
Signal white
2 lines
Galltec+Mela
eStat10 DUO
Page 1 of 4