DSE6110-200 pages
® DSEULTRA®
STARTING
WITH
QUALITY. SPECIFICATION
The DSE6110 is an Auto Start
ControlModule and the DSE6120 is
an AutoMains (Utility) Failure
ControlModule for single gen-set
applications. Bothmodules have
been designed to work with
electronic and non electronic
engines providing advanced engine
monitoring and protection features.
Themodules include a backlit LCD
display which clearly shows the
status of the engine at all times.
Theymonitor, speed, frequency,
voltage, current, oil pressure,
coolant temperature and fuel level.
Themodules have also been
designed to display the warning
and shutdown status of the engine.
Bothmodules include six digital
inputs and six outputs. Two of the
outputs are configurable on the
magnetic pick-up version and all six
are configurable on the Canbus
version. Themodules can either be
programmed using the front panel
or by using the DSE Configuration
Suite PC software.
CONFIGURATION
The modules can be configured using
the front panel or by remote PC using
a USB connection lead and the DSE
Configuration Suite PC software.
FEATURES
• CAN and magnetic pick-up
versions
• PC and front panel configurable
• 6 digital inputs/ 3 analogue inputs
• 6 outputs (2 configurable on
Magnetic Pick-Up, 6 configurable
on Canbus version)
• 3 Phase generator and mains
(utility) voltage monitoring (mains
on DSE6120 only)
• Event log (10)
• Configurable timers
• Automatic shutdown or warning
when fault conditions are detected
• Remote start on or off load
• Engine pre-heat
• Advanced metering capability
• Engine hours counter
• Red LED indicators for warning or
shutdown
• Text LCD Display
• Protected Solid State Outputs
(PSS)
• Test button
BENEFITS
• Transfer between mains (utility) and
generator power (DSE6120 only)
• Hours counter provides accurate
information for monitoring and
maintenance periods
• User-friendly set-up and button
layout
• Multiple engine parameters are
monitored simultaneously
• Module can be configured to suit
individual applications
• Wide range of engines can be
specified
• Uses the DSE Configuration Suite
PC Software for simplified
programming
• IP65/NEMA 12 rating offers
advanced resistance to water
ingress when gasket is fitted
• License free PC software
OPERATION
Manual Mode
• The engine is started using the
Start button on the front of the
module.
• Once pressed the module
instructs the engine to initiate its
pre-heat sequence and then start
the engine.
• To stop the engine the Stop
button on the front of the module
should be pressed.
Automatic Mode
• The Auto button needs to be
pressed to put the unit in Auto
Mode.
• The module start sequence is
initiated by the activation of the
remote start input.
• The pre-heat sequence is then
initiated and the engine is started.
• To stop the engine the remote
start signal needs to be removed
or the Stop button on the module
needs to be pressed.
OVERSPEED PROTECTION
The engine over speed trip setting
can be calibrated for 50Hz or 60Hz
nominal operation. During engine
cranking and for a user configurable
time after the engine starts running,
all alarm conditions are suspended
to allow the engine to reach its
optimum running speed.
ELECTRONIC ENGINE
COMPATIBILITY
• CAT
• Cummins
• Deutz
• John Deere
• MTU
• Perkins
• Scania
• Volvo
• Generic
• Plus additional manufacturers
DC SUPPLY
8V to 35V Continuous
CRANKING DROPOUTS
Able to survive 0V for 50mS, providing supply
was at least 10V before dropout and supply
recovers to 5V. This is achieved without the
need for internal batteries. LEDs and backlight
will not be maintained during cranking.
MAXIMUMOPERATING CURRENT
178mA at 12V 95mA at 24V
MAXIMUMSTANDBY CURRENT
88mA at 12V 50mA at 24V
GENERATOR INPUT RANGE
15V to 333V AC (L-N) absolute maximum
50Hz - 60Hz (min 15V AC)
CHARGE FAIL/EXCITATION RANGE
0V to 35V
VOLTAGE RANGE
0.5V RMS minimum
FREQUENCY RANGE
10,000 Hz (max)
15V to 333V AC (L-N) absolute maximum
25V to 576V AC (L-L) absolute maximum
50Hz - 60Hz (min 15V AC)
OVERALL
216mm x 158mm x 42mm
8.5” x 6.2” x 1.6”
PANEL CUT-OUT
182mm x 137mm
7.2” x 5.4”
MAXIMUMPANEL THICKNESS
8mm. 0.3”
DSE6110 & DSE6120
AUTO START & AUTOMAINS (UTILITY) FAILURE CONTROLMODULES
DC SUPPLY
MAGNETIC PICKUP
OUTPUTS
DIMENSIONS
MAINS (UTILITY) SENSING INPUT RANGE
(DSE4420 ONLY)
OUTPUT A (FUEL)
2 Amp DC at supply voltage
OUTPUT B (START)
2 Amp DC at supply voltage
AUXILIARY OUTPUTS C,D
2 Amp DC at supply voltage