dse705-41300 pages
®
DSEAts
DSE705/4130
ENVIRONMENTAL TESTING STANDARDS
ELECTRO-MAGNETIC COMPATIBILITY
BS EN 61000-6-2
EMC Generic Immunity Standard for
the Industrial Environment
BS EN 61000-6-4
EMC Generic Emission Standard for
the Industrial Environment
AUTO TRANSFER SWITCH
FEATURES
The DSE705 and DSE4130 are
Transfer Switch Control Modules
that have been designed to monitor
the mains (utility) supply.
When the mains (utility) power fails,
the module will send a start request
to the generator control unit. When
the generator is up and running the
module transfers the load across.
When the mains (utility) returns, the
module transfers the load back and
removes the start command. The
generator should then begin its
shutdown procedure.
ELECTRICAL SAFETY
BS EN 60950
Safety of Information Technology Equipment,
including Electrical Business Equipment
The modules can be configured to
follow the users’ pre-set start and
stop sequences.
TEMPERATURE
BS EN 60068-2-1
Ab/Ae Cold Test -30 oC
BS EN 60068-2-2
Bb/Be Dry Heat +70 oC
The DSE4130 case includes a
closed back.
VIBRATION
BS EN 60068-2-6
Ten sweeps in each of three
major axes
5 Hz to 8 Hz @ +/-7.5 mm,
8 Hz to 500 Hz @ 2 gn
HUMIDITY
BS EN 60068-2-30
Db Damp Heat Cyclic 20/55 oC
@ 95% RH 48 Hours
BS EN 60068-2-78
Cab Damp Heat Static 40 oC
@ 93% RH 48 Hours
SHOCK
BS EN 60068-2-27
Three shocks in each of three major axes
15 gn in 11 mS
DEGREES OF PROTECTION
PROVIDED BY ENCLOSURES
BS EN 60529
IP65 - Front of module when installed into the
control panel with the sealing gasket (to be
ordered seperately).
COMPREHENSIVE FEATURE LIST TO SUIT A WIDE VARIETY
OF ATS APPLICATIONS
2
CLOSE TO NEUTRAL
POSITION
REMOTE START
START/RUN OUTPUT
-VE
NEGATIVE DC OUTPUT
DC POWER
SUPPLY 8-35V
-VE
DSE705/4130
7
OTHER
MAINS (UTILITY) SENSING
CLOSE MAINS NEGATIVE
DC OUTPUT
CLOSE GENERATOR
NEGATIVE DC OUTPUT
GENERATOR SENSING
VOLTS
VOLTS
-VE
-VE
1ph
2ph
3ph
N
1
1
ALL OUTPUTS ARE -VE SWITCHING SOLID STATE
1ph
N
ISSUE 3
"