Generating set Auto Synchroniser and load sharer.
APPLICATIONS
Isochronous load sharing in island mode
UNIGEN will be used on generator sets that require synchronising, load sharing and paralleling features. UNIGEN can be used
to parallel up to 8 gensets together. One UNIGEN is needed per
generator set.
Mobile gensets
With its digital « Super Droop » function (wireless load share),
unique on the market, UNIGEN makes the mobile gensets coupling simple where the communication between the UNIGENS
is useless.
ADVANTAGES
SUPER DROOP (digital), at +/-0,25Hz
No communication between UNIGENS is needed to achieve the
coupling. The curve is almost isochronous at +/-0,25Hz.
A51Z2
Compatible with all speed governors: UNIGEN is equiped
with an analogue output (+/- 10V adjustable) for speed control.
Barber Colman / Woodward
MTU MDEC
Cummins
GAC
Volvo
Deutz EMR
Heinzmann
Perkins
Scania
Compatibility with all AVR :
UNIGEN is equipped with an analogue output (+/-10V adjustable) and is in this way compatible with all AVR.
STAMFORD
MARELLI MOTORI
BASLER
MARATHON
AVK
LEROY SOMER
MECC ALTE SPA
ALL the settings are adjusted with potentiometers
No computer needed!!
With a microprocessor of 16 bits, UNIGEN is, regarding numerical technology, very fast.
CANBUS “plug & Play”
The address of each Unigen doesn’t need to be adjusted. All
Unigens connected on the CANBUS will automatically detect the
other one.
FUNCTIONS
Synch check relay ‘SYNC OK’
UNIGEN controls the difference of voltage, frequency and phase
between the generator to be paralleled and the bus bar. The sync
check relay “SYNC OK” authorizes the closing of the generator
breaker either in Automatic mode or Manual mode.
Automatic & Manual Synchronisation:
The automatic mode of UNIGEN modies the voltage, the frequency and the phase in order to enable quick and precise coupling. Using the manual mode, the speed can be adjusted by an
external 10kOhms potentiometer.
Power load sharer (kW & kVAR):
It manages load and unload ramps during the launch and the
stop of the group. It can manage groups of various power and/or
with electronic speed regulators from different marks.
Load dependant start
This fonction is activated to start/stop slave generator sets in accordance with the load demand.
Reverse kW protection
The relay ‘REV kW’ closes on reverse power.
Analogue kW output
Compatible with PLC and 0-5 V, 0-20 mA or 4-20 mA gauges.