BP+ RANGE0 pages
product information
battery chargers
BP+ RANGE
FEATURES
• Economic version
• Protections: Short circuit, overload, overvoltage, over temperature and reverse
power (diode integrated)
• Cooling by free air convection
• Can be installed on DIN rail TS-35/7.5 or TS-35/15
• LED indicator for power on
• 100% full load burn-in test
• 3 years warranty
BP+ 0324M
BP+ 1012M
BP+ 0524M
12 V
24V
12V
24V
RATED CURRENT
battery chargers
BP+ 0512M
DC VOLTAGE
5A
3A
10A
5A
CURRENT RANGE
0 ~ 5A
0 ~ 3A
0 ~ 10A
0 ~ 5A
RATED POWER
60 W
60 W
120 W
120 W
RIPPLE & NOISE (Max.)
100mVp-p
120mVp-p
24 ~ 28 V (26.4V)
12 ~ 14 V (13.2V)
24 ~ 28 V (26.4V)
(+/-) 0.5%
(+/-) 1.0%
SETUP, RISE TIME
1500ms, 60ms/230VAC
HOLD UP TIME (Typ.)
16ms/230VAC
INFORMATION
Please adjust output voltage required with the potentiometer according to the battery charger
VOLTAGE RANGE
90 ~ 264VAC
FREQUENCY RANGE
product information
120mVp-p
12 ~ 14 V (13.2V)
LOAD REGULATION
INPUT
100mVp-p
VOLTAGE ADJ. RANGE (by default)
LINE REGULATION
OUTPUT
47 ~ 63Hz
127 ~ 370VDC
EFFICIENCY (Typ.)
83%
87%
84%
87%
AC CURRENT (Typ.)
1.6A/115VAC / 0.9A/230VAC
1.6A/115VAC / 0.9A/230VAC
2.65A/115VAC
1.45A/115VAC
INRUSH CURRENT (Typ.)
20A/115VAC
LEAKAGE CURRENT
35A/230VAC
<1mA / 240VAC
OVERLOAD
PROTECTION
3000ms, 60ms/115VAC at full load
12ms/115VAC at full load
OVER VOLTAGE
105 ~ 130% rated output power
Protection type: constant current limiting with auto-recovery after fault condition is removed
14 - 17V
29 - 33V
14 - 17V
29 - 33V
Protection type : shut down o/p voltage, re-power on to recover
OVER TEMPERATURE
20 ~ 95% RH non condensing
STORAGE TEMP, HUMIDITY
(-)40 ~ (+)85°C, 10 ~ 95% RH
TEMP. COEFFICIENT
(+/-)0.03%/°C (0 ~ 50°C)
VIBRATION
Component: 10 ~ 500Hz, 2G 10min./1cycle, period for 60min. each along X, Y, Z axes ; Mounting : Compliance with IEC60068-2-6
WITHSTAND VOLTAGE
I/P-O/P:3KVAC
ISOLATION RESISTANCE
I/P-O/P, I/P-FG, O/P-FG:>100M Ohm / 500VDC / 25°C / 70% RH
EMI CONDUCTION & RADIATION
Compliance with EN55011, EN55022 (CISPR22), EN61204-3 Class B
HARMONIC CURRENT
Compliance with EN61000-3-2,-3
EMI IMMUNITY
SAFETY & EMC
(-)20 ~ (+)70°C (Refer to output load derating curve)
WORKING HUMIDITY
ENVIRONMENT
110°C (+/- 5°C) Protection type : shut down o/p voltage, re-power on to recover
WORKING TEMPERATURE
Compliance with EN61000-4-2, 3, 4, 5, 6, 8, 11, ENV50204, EN55024, EN61000-6-2, EN61204-3, heavy industry level, criteria A
I/P-FG:1.5KVAC
O/P-FG:0.5KVAC
MTBF
486Khrs min MIL-HDBK-217F (25°C)
456Khrs min MIL-HDBK-217F (25°C)
DIMENSION (W x H x D)
32 x 125.2 x 102mm
32 x 125.2 x 102mm
40 x 125.2 x 113.5mm
40 x 125.2 x 113.5mm
PACKING
OTHERS
0.51kg
0.51kg
0.57kg
0.57kg
All parameters NOT specially mentioned are measured at 400VAC input, rated load and 25°C of ambient temperature.
Ripple & noise are measured at 20MHz of bandwidth by using a 12’’ twisted pair wire terminated with a 0.1 uf & 47 uf parallel capacitor.
NOTES
The battery charger is considered a component which will be installed into nal equipment. The nal equipment must be re-conrmed that it still meets EMC directives
Installation clearances: 40mm on top, 20mm on bottom, 5mm on the left and right side are recommended when loaded permanently with full power. In case the adjacent
device is a heat source, 15mm clearance is recommended.
Derating may be needed under low input voltage and extreme temperature. For 115V, please check the derating curve.
v_062015
www.cretechnology.com
"