RP10, 1-phase monitoring0 pages
C-mac
®
1-phase monitoring relay RP10
Monitoring of 1-phase supply voltage
Separate adjustments of minimum and maximum limits
1- or 2-pole relay output
DC supply or AC supplies up to 230 VAC
Made in accordance with the
and EMC regulations
The C-mac® module type RP10 monitors its own 1-phase
Functional diagram:
supply voltage and checks that it is within the adjusted
minimum and maximum limits, and in that case, the out- setpoint
put relay is activated.
hysteresis
The modulecan operate from 80% to 120% of the nominal
nom.sup.
supply voltage.
actual sup.
hysteresis
setpoint
Technical data:
Supply voltage:
Power consumption:
Operation temp.:
Humidity:
Adjustments:
Upper limit:
Lower limit:
Hysteresis:
Indications:
Green LED:
Red LED:
Max. load, relay:
24 VDC, 24 VAC, 115 VAC or
230 VAC +/- 20%
2,5 VA
-20°C til +60°C
0 - 90% RH, non-condensing
Potentiometer, 105 to 120%.
Potentiometer, 80 to 95%
1% of the nominal supply.
Supply voltage connected
Relay active
1-pole: 8 A - 250 VAC
2-pole: 5 A - 250 VAC,
ohmic load
relay
Ordering guide:
Supply
24 VDC
24 VAC
115 VAC
230 VAC
x = output relay:
Type no.
RP10-x-0-024
RP10-x-1-024
RP10-x-1-115
RP10-x-1-230
1 = 1-pole
2 = 2-pole
Mechanical dimensions:
38 mm
C-mac
EMC and safety regulations.
6
5
7
4
11
+
Supply
6
0
4
10
6
0
10 sec
8
8
2
Level
Delay
Relay
9
3
1
4
2
Supply
8
2
Control module
76 mm
Emmision:
EN 50 081 - 1
Immunity:
EN 50 082 - 2
Safety:
EN 60 730
Approvals: The units are produced in accordance with the CE
og low voltage regulations.
Connections:
74 mm
Materials and weight:
10
pin 8-9-11:
2-pole version only
Housing:
NORYL-SE-1, grey, self-extinguishing
Housing bottom: NORYL SE-1, GFN-2, black,
self-extinguishing
Terminals:
Nickel-plated brass
Weight:
110 g
Comadan
Produktion a/s
4-5
"