trouble shooting0 pages
Compressor Seems Excessively
Noisy At Start-up (High Pitch)
I Insure oil feed lines are open (oil solenoid).
I Check oil pressure at compressor manifold
with a gauge.
Compressor Makes a Loud Grinding
Noise at Start-up
I Oil solenoid is leaking oil into the
compressor while off. Repair or replace
oil solenoid.
I Compressor filling with refrigerant while
off. Determine refrigerant source and
eliminate during compressor off cycle.
I Check evaporator superheat.
Suction
Access Port
Min Pressure
10” vacuum
Unloading Valve
Energize coil to
load compressor
Suction Service Valve
Max temp 65F, 6” from
the service valve
Motor Temperature
(5K thermistor connection
on terminal plate)
Economizer/
Subcooler Port
(not shown)
Rotalock valve,
7/8” sweat
connection
must have
15F - 20F
superheat
Discharge
Service Valve
Max Temp 230F,
6” from the service
valve (5K thermistor
strapped to
discharge line)
Screw Compressor
Troubleshooting
Guide
Oil Port Access Port
(1/4” Schrader, not shown)
Liquid
For field gauge connections
Injection Port
Oil Press Transducer
(3/8” Flare,
Max Press Differential
used if necessary)
(discharge - oil) 50psi
VI (Volume Index)
Valve energize coil at
Oil Inlet Min Differential Pressure
(Oil - Suction) 45psi
pressure ratios > 5:1
(3/8” Flare)
Discharge Access Port
Max Press Differential
(discharge - suction) 350psid
Compressor Periodically Makes
Loud Noise or Becomes Very Quiet
for a Short Time
Caution: Never Run the
Compressor in Reverse!
06T Model
I Check for excessive liquid/oil return
to compressor.
Support/Contact
I Call Application Engineering for further
assistance at 800.532.5036.
Carlyle Compressor Division
P. O. Box 4808
Syracuse, NY 13221
Phone: 800.532.5036
Fax: 315.432.3274
0604
Lit. No. 574-081 Rev. A