DJU Lead-Calcium Battery0 pages
FLOODED
CY
TU
RN
RE
12-1102
RE
CL
E
LEAD
DJU Lead-Calcium Battery
Every battery
100%
FOR SWITCHGEAR & CONTROL APPLICATIONS
capacity tested
CAPACITIES FROM 110 TO 200 AMPERE-HOURS
INDIVIDUAL POSTS IN A MULTI-CELL BATTERY
C&D Technologies’ flooded batteries are
engineered to provide superior performance
and reliability over the life of the product.
These batteries are designed using proprietary
techniques and quality components and
materials for reduced maintenance and
extended battery life.
APPLICATIONS
•t Electric Utility Substations
•t Manufacturing Facilities
t
- Assembly Lines
- Process Controls
- Communication Systems
•t Petrochemical Processing
tPlants
•t Pipelines
•t Emergency Systems
DJU SERIES BATTERY
FEATURES & BENEFITS
RELIABILITY
COST SAVINGS
•t Reliable tongue and groove jar-to-cover
seal design provides increased
adhesive coverage area — offering
unprecedented seal integrity during
service
•t Unique jar design facilitates installation
•t Top suspended positive plate design
allows free downward growth without
pressure on jar, cover, or post seal —
extending reliability and product life
•t Recessed vent area to collect water
and acid spills, keeping them away from
posts and cover — lowering
maintenance and clean-up costs
•t Wrapped separator design extends
cycle life — improving product reliability
•t Enhanced post seal design allows post
growth without transmitting forces to
cover
•t Compact, optimized product size nets
up to 40% floor space reduction —
saving valuable space
EASY MAINTENANCE
•t All posts and connectors reside above
the jar cover
•t Individual posts allow monitoring of
individual cell performance in a
multi-cell container
•t Individual posts use standard
lead-plated copper connectors
decreasing connection resistance
•t Optional terminal and connector cover
available (P/N RD00907-“L”)
SAFE OPERATION
•t Self extinguishing features (LOI >32)
of flame retardant (FR) cover and jar
material — providing added protection
•t Low evaporation, flame arrestor vents
protect against an external source
igniting hydrogen gas within the cells —
improving safety
The new 20-year design life DJU
batteries incorporate these benefits
in a transparent container for visual
inspection of plates and has individual
posts for cell voltage readings.
SPECIFICATIONS
t Recommended float voltage ranget
2.20–2.25 volts per cell (1.215 specific gravity)
t Specific gravity of electrolyte @77°F (25°C)t1.215 (standard)
t Cover materialt
High impact, PVC, LOI>32, UL94-V0
t Container materialt
Transparent, high-impact PVC, LOI>32, UL94-V0
t Separator materialt
U-wrapped, microporous with fibrous mat
t Terminal typet
Rectangular lead post, two for every cell
t Safety ventt
Flame arrestor/low evaporation type
C&D capacity tests every
DJU battery to 100% of
published rating which
ensures 100% capacity
out-of-the-box (no need to
field cycle the batteries to
reach rated capacity). This
saves time and money for
users.
12-1102/0615/CDttttttttttt
www.cdtechno.com
"