Technical data sheet CM24-..0 pages
Technical data sheet
CM24-..
Damper actuator for operating air control
dampers in ventilation and air-conditioning
systems for building services installations
•tFor air dampers up to approx. 0.4 m2
•tTorque 2 Nm
•tNominal voltage AC/DC 24 V
•tControl: Open-close or 3-point
Type overview
Type
Direction of rotation
CM24-L
counter-clockwise (ccw)
CM24-R
clockwise (cw)
.
.
.
.
.
.
.
.
.
.
.
Technical data
Electrical data
Functional data
Nominal voltage
Nominal voltage range
Power consumption In operation
At rest
For wire sizing
Connection
AC 24 V, 50/60 Hz / DC 24 V
AC/DC 19.2 ... 28.8 V
0.5 W @ nominal torque
0.2 W
1 VA
Cable 1 m, 3 x 0.75 mm2
Torque (nominal torque)
Direction of rotation
Manual override
Angle of rotation Without limit
With limit
Min. 2 Nm @ nominal voltage
See «Type overview»
Gear disengagement with magnet
Endless
Fixed 315° or 0 ... 287.5° with mechanical end stops,
can be adjusted in 2.5° increments
75 s / 90°
Max. 35 dB (A)
Mechanical, pluggable
(with integrated magnet for gear disengagement)
Running time
Sound power level
Position indicator
Safety
Protection class
Degree of protection
Mode of operation
Rated impulse voltage
Control pollution degree
Ambient temperature
Non-operating temperature
Ambient humidity
Maintenance
III Safety extra-low voltage / UL Class 2 Supply
IP54 in any mounting position
NEMA2, UL Enclosure Type 2
CE according to 2004/108/EC
cULus according to UL 60730-1A and UL 60730-2-14
and CAN/CSA E60730-1:02
Certified to IEC/EN 60730-1 and IEC/EN 60730-2-14
Type 1 (EN 60730-1)
0.8 kV (EN 60730-1)
3 (EN 60730-1)
–30 ... +50°C
–40 ... +80°C
95% r.H., non-condensating (EN 60730-1)
Maintenance-free
Dimensions
Weight
See «Dimensions» on page 2
Approx. 220 g
EMC
Certification
Dimensions / Weight
Safety notes
!
www.belimo.com
•t The actuator is not allowed to be used outside the specified field of application, especially in
aircraft or any other form of air transport.
•t Assembly must be carried out by trained personnel. Any legal regulations or regulations
issued by authorities must be observed during assembly.
•t The device may only be opened at the manufacturer‘s site. It does not contain any parts that
can be replaced or repaired by the user.
•t When calculating the required torque, the specifications supplied by the damper manufactur
ers (cross section, design, installation site), and the air flow conditions must be observed.
T2-CM24-.. • en • v1.2 • 08.2008 • Subject to changes
/2