http://www.belimo.ch/pdf/e/CM24-SR-T-.._1_1_en.pdf0 pages
Technical data sheet
CM24-SR-T-..
Modulating damper actuator for operating
air control dampers in ventilation and airconditioning systems for building services
installations
• For air dampers up to approx. 0.4 m2
• Torque 2 Nm
• Nominal voltage AC/DC 24 V
• Control: modulating DC 0 ... 10 V
• Position feedback DC 2 ... 10 V
• Connecting terminals
Type overview
Type
Direction of rotation
CM24-SR-T-L
Y = 0 V left end stop position 0
CM24-SR-T-R
Y = 0 V right end stop position 0
Technical data
Electrical data
Nominal voltage
Nominal voltage range
Power consumption In operation
At rest
For wire sizing
Connection
Functional data
Torque (nominal torque)
Control Control signal Y
Operating range
Position feedback (Measuring voltage U)
Posotion accuracy
Direction of rotation
Manual override
Angle of rotation
Running time
Sound power level
Position indication
Safety
Protection class
Degree of protection
AC 24 V, 50/60 Hz
DC 24 V
AC/DC 19.2 ... 28.8 V
1 W @ nominal torque
0.5 W
2 VA
Terminals for 4 x 1.5 mm2 CU wire
or 4 x 1.0 mm2 CU litz wires
Min. 2 Nm @ nominal voltage
DC 0 ... 10 V, typical input impedance 100 kΩ
DC 2 ... 10 V
DC 2 ... 10 V, max. 1 mA
±5%
See «Type overview»
Gear disengagement with magnet
Max. 95° , limited on both sides by means of adjustable,
mechanical end stops
75 s / 90°
Max. 35 dB (A)
Mechanical, pluggable
(with integrated magnet for gear disengagement)
Mode of operation
Rated impulse voltage
Control pollution degree
Ambient temperature
Non-operating temperature
Ambient humidity
Maintenance
Dimensions
Weight
See «Dimensions» on page 2
Approx. 160 g
EMC
Certication
Dimensions / Weight
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
III Safety extra-low voltage / UL Class 2 Supply
IP20 in any mounting position
NEMA1, UL Enclosure Type 1
CE according to 2004/108/EC
cULus according to UL 60730-1A and UL 60730-2-14
and CAN/CSA E60730-1:02
Certied to IEC/EN 60730-1 and IEC/EN 60730-2-14
Type 1 (EN 60730-1)
0.8 kV (EN 60730-1)
2 (EN 60730-1)
–30 ... +50°C
–40 ... +80°C
95% RH, non-condensating (EN 60730-1)
Maintenance-free
Safety notes
!
www.belimo.com
• The actuator is not allowed to be used outside the specified field of application, especially in
aircraft or any other form of air transport.
• Assembly must be carried out by trained personnel. Any legal regulations or regulations
issued by authorities must be observed during assembly.
• The mechanical end stops for restricting the angle of rotation are only allowed to be removed
for adjustment purposes. It is essential for them to be in place during operation.
T2-CM24-SR-T-.. • en • v1.1 • 04.2008 • Subject to changes
1/2