Technical data sheet CM230-T-..0 pages
Technical data sheet
CM230-T-..
Damper actuator for adjusting air dampers
in ventilation and air-conditioning systems
in buildings
•tFor air damper up to approx. 0.4 m2
•tTorque 2 Nm
•tNominal voltage AC 100 ... 240V
•tControl: Open-close or 3-point
•tWith connecting terminals
Type overview
Type
Direction of rotation
CM230-T-L
counter-clockwise (ccw)
CM230-T-R
clockwise (cw)
Technical data
Electrical data
Functional data
Nominal voltage
Nominal voltage range
Power consumption In operation
At rest
For wire sizing
Connection
AC 100 ... 240V, 50/60 Hz
AC 85 ... 265 V
1.5 W @ nominal torque
1W
3 VA
Terminals for 3 x 1.5 mm2 CU wire
or 3 x 1.0 mm2 CU strands
Torque (nominal torque)
Direction of rotation
Manual override
Angle of rotation without limit
with limit
Min. 2 Nm @ nominal voltage
See «Type overview»
Gear disengagement with magnet
endless
315° fixed or 0 ... 287.5° with mechanical end
stops, adjustable in 2.5° increments
75 s / 90°
Max. 35 dB (A)
Mechanical, pluggable
(with integrated magnet for gear disengagement)
Running time
Sound power level
Position indication
Safety
EMC
Low voltage directive
Certification
Mode of operation
Rated current voltage
Control pollution degree
Ambient temperature
Non-operating temperature
Ambient humidity
Maintenance
Dimensions / Weight
Protection class
Ensuring protection against contact of live parts
must be taken into account at the time of installation
CE according to 2004/108/EC
CE according to 2006/95/EC
Certified to IEC/EN 60730-1 and IEC/EN 60730-2-14
Type 1
2.5 kV
2
–30 ... +50°C
–40 ... +80°C
95% r.h., non-condensating
Maintenance-free
Dimensions
Weight
See «Dimensions» on page 2
Approx. 220 g
Safety notes
!
www.belimo.com
•t The actuator is not allowed to be used outside the specified field of application, especially in
aircraft or in any other airborne means of transport.
•t Caution: Power supply voltage !
•t The actuator, in particular the contacting area, must be protected against interventions from
outside, in particular against inadvertent contact with live components, in order to exclude
the possibility of short circuits and the danger of electrical shock.
•t Assembly must be carried out by trained personnel. Any legal regulations or regulations
issued by authorities must be observed during assembly.
T2-CM230-T-.. • en • v1.0 • 06.2011 • Subject to changes
/2