CombiView DFON0 pages
CombiView DFON
Graphical display
Main features
Graphical display with
Option: Two configurable relay
backlight
Showing errors and limits by
steady or flashing colours
Fits Baumer CombiSeriesTM
(Ø80 mm FlexHousing)
Hygienic design
outputs
Programmable by touch screen
Easy and fully programmable
with FlexProgrammer 9701
ATEX
Applications
Remote display fits for all 4 - 20 mA transmitter
all mounting, panel mounting and pipe mounting
W
t
Technical Data
Relay
Measuring range
Connections
3.5…23 mA (normal working range
4...20 mA)
2 screw terminals for loop power, signal
4 screw terminals for relay outputs
Accuracy
≤ ±0.1% of input span within
-10...70 °C
≤ ±0.2% of input span within
-30...-10 °C / 70...80 °C
Loop voltage drop
Sample time
Two levels depending on chosen backlight
brightness @ 20 mA :
- Low bright backlight (<40%) :
Max. 4V @23 °C
- High bright backlight (>40%) :
Max. 6.5V @23 °C
≤ 1 second. Typical 0.3 second
Start-up time
≤ 5 second
User-configurable data
Measuring range
4...20 mA
Error/warning indication
Individually configurable display and
backlight indication in white, green or red
colour, steady or flashing light. Configurable limits between 3.5 and 23 mA
Zoom on range
Minimum 2 mA of input span
Damping
60 Vp
Load Current
75 mA
Max On resistance
10 Ohm
The built in relays are not activated
as standard. They can be activated at
purchase or SW activation code can be
purchased later.
Display
Type
FSTN Graphically LCD
Measuring range
-9999...99999
Digit height
Max. 22 mm
EMC data
Immunity
EN 61326
Emission
EN 61326
EMC immunity Influence
≤ ±1% of input FS
Communication
FlexProgrammer 2-way communication for configuration.
Test conditions
Operating temperature
23°C ± 2 °C
2 to 30 points
Measuring unit
(standard selectable)
2 solid state relays
Voltage
0...30 seconds
Linearization table
Contacts
Design and specifications subject to change without notice
Input
°C, °F, K
bar, mbar, kPa, MPa, psi, kg/cm2, mmHg,
mH2O, atm, "Hg, mHg, "H2O, %, l/h, Ton,
m3, m3/h, Hz, mS, mV, V, ohm, Hz, sec,
%, mA, or user defined (programmable
with FlexProgrammer)
8 x 20 pixels matrix
Dec. point position
www.baumer.com
xxxxx, xxxx.x, xxx.xx, xx.xxx,
x.xxxx, .xxxxx, AUTO
EN/215-01-30
User defined unit
Data sheet D21.09
Page 1 / 5
"