ELECTRIC HEATERS MBE0 pages
ELECTRIC HEATERS I njft
MBE Series V8»
Designed to be installed on the fans
discharge side. The minimum air speed
through the heater must be 1,5 m/s.
Maximum air temperature through the
heater: 40°C.
The batteries are fitted with:
- Armoured heating element.
- Double protection circuit to connect to
the battery control circuit by means of
a safety overheat automatic thermostat
connected in series with another safety
overheat manual reset thermostat
(RESET).
- Wiring box IP4-3.
Available temperature sensors in the
duct, ambient temperature sensors
and speed controllers to complete
the installation and to adjust the air
temperature according to every need.
SELECTION EXAMPLE
DATA:
-Airflow: 700 mVh (Q]
- Temp, of supplied air: 5°C
- Temp, of exhausted air: 27°C
ELECTRIC HEATER POWER REQUIRED
P = QxO,36xAT = 700x0,36x22 = 5544 W
HEATER SELECTION MBE-200/50T or
MBE-250/60T (Diagram 2]
The final selection depends on
- Total system pressure drop
- Desired sound level
- Available space
150
ip (Pa;
125
100
75
50
25
0
MBE - Pressure drop Ap (Pa)
1-MBE-100/04B 2-MBE-125/12B-16IV21B 3- M BE-200/50T ■ 250/60T ■ 400/90T 4-MBE-355/90T 5-MBE-31S/90T | w | |||
© |
8 9 (m/s)
Diagram 1
AT
(°C)
40
30
20
10
0
100
MBE - Air temperature increases AT (°C)
ft |
: 4°o w |
200
300
400 500
1000
2000 3000 4000 5000 6000 m /h
Diagram 2
Electric heaters MBE
www.solerpalau.com
"