0.6/1 kV PVC insulated cable
1. Executive standard
This product is designed and manufactured in
accordance with GB/T12706-2008. the flame-retardent
property meet the requirement ruled in GB/T19666.
2. Application
This product applies to the lines with the rated AC
volatge at 0.6/1 KV for power transmission and
distribution.
3. Nomal service condition
3.1 The allowable working tern for cable < 70°C .
When standing in short circuit condition(the longest time
is less than 5sec), conductor section area<300mm2,
the max tern for cable conductor is less than 160°;
Conductor section area > 300mm2, The max tern for
cable conductor <140°C .
3.2 The environment tern for the laying of cable shall be
no less than 0°, if not, pre-heating must be made.the
min bending radium should be no less than: Single core
cable without armor 20D, with armor 15D; three core
cable without armor 15D, with armor 12D. (D is the real
outer diameter)
3.3 Conductor DC resistance should comply with the
rules in GB/T3956
3.4 working frequency power withstand test: 3.5kV/5min
no breakthrough.
3.5 flame-retardent cable can withstand the clustered
burning test ruled in GB/T18380.3, and the smoke
density during burning meet the requirement of GB/
T1765.1. Also the content of HCL deriving from the
burning gas should be < 100mg/g.