2U Liquid-Cooled Mercury shelf0 pages
2U Liquid-Cooled Mercury shelf
The modern approach for Industrial power in challenging environments
Features
•
Semi-Sealed, to protect units from their Physical Environment
•
Higher power Density than convection cooled
equivalent units
•
Modular design for higher system availability
•
280kW of AC/DC Conversion in a 44U Cabinet
Uses & Benefits
Specifications
The Liquid Cooled Mercury Shelf when combined with the Mercury rectifier products is
INPUT
designed to be part of a high power DC system. Each 2U shelf is self contained with input
AC connector and an output DC Terminal
Block. The shelf also has inlet & outlet connec-
90 to 300 VAC, 47 to 63Hz
AC Range:
OUTPUT
Voltage:
Power:
Current:
Max of 59VDC
up to Max of 12,900Watts
up to Max of 480A
ALARMS
TTL compatible signals for: AC OK, Output
OK
Electronics Controls for: Remote Inhibit,
Remote Program, Unit Present.
tors for the cooling liquid and an alarm & control connector. Using the self-cooled rectifiers’
fan to force the waste heat (from the rectifiers) through the integral cooling element the
system releases very little heat outside of the
shelf. Shelf cooling is completed via the internal Heat-Exchanger with an external coolant
chiller.
ENVIRONMENTAL
Normal operation:
Storage Temp:
Humidity:
+10° to + 55°
C
C
-10° to + 85°
C
C
0-95% non-condensing
MECHANICAL
Weight:
Module Dimensions:
Mounting:
25 Lbs (11.4)
Height: 3U
Width : 17.5” (Std 19” shelf mounting)
Depth: 24.25” (616mm)
19” or 23” with extensions
Adjustable Rear mounting ears available.
Ordering Information
Part no.
144556
Description
2U Water Cooled Rectifier Shelf
www.tdipower.com
© Copyright 2008, Transistor Devices, Inc. 17552RJA
DEMANDING APPLICATIONS DEMAND TDIPOWER
This document is believed to be correct at time of publication and Transistor Devices, Inc. accepts no responsibility for consequences from printing errors or inaccuracies.