92 series0 pages
Series 92
Electric Actuator
Standard Features
•Motor: Reversing, brushless, capacitor-run 115 VAC
50/60 Hz, single phase
• Overload protection: Integral thermal overload
protection for motor windings with automatic reset
• Gear train: Permanently lubricated, solid gear that is
Rockwell hardened
• Corrosion resistant housing: Thermally bonded baked
powder coating rated Type 4X with stainless steel trim
• ISO mounting configuration
• Conduit: Two 1/2” NPT conduit entries to eliminate
cross feed between control, feedback, and power
signals
UL-508
Listed
Options
• Position indication: Highly visible beacon position
indicator for positive indication of valve position
• Declutchable manual override: Pull up on indicator knob,
insert 5/8” wrench onto flats and rotate in the
appropriate direction (CCW for open, CW for close).
Models with handwheel override do not require a
wrench. Simply push down on handwheel until engaged
with cam and rotate
• Limit switches: Standard end of travel limit switches
can be used for light indication
(not to be use with PLC for position confirmation)
• Extended duty cycles: Our extended duty cycles are ideal
for modulating and high cycling applications
• Output torque: Series 92 electric actuators have an
output torque range from 400 in./lbs. to 2,000
in./lbs.
115 VAC
Amp
Duty
Draw
Cycle
230 VAC
Amp
Duty
Draw
Cycle
12 VDC
Amp
Duty
Draw Cycle
• Mechanical brake
• Transmitter
• Failsafe battery back up (Protek)
• Voltages
• UL1203 explosion proof enclosure
See page 194 for more details regarding options.
• CE compliant motor: All 115 VAC and 230 VAC motors
are CE compliant and stamped as such
Torque
(in/lbs)
• Positioner (modulating PCB)
• Local remote station
• Corrosion resistant mounting: Mounting is with PPG or
stainless steel bracket, stainless steel coupling, and
stainless steel hardware
Model
• Heater and thermostat
• Two-wire control
• Captivated SS hexhead slotted cover screws
Engineering Data
• Feedback potentiometer
• Cycle length control module (CLC)
• Enclosure: Weatherproof enclosure rated Type 4X has
a thermally bonded powder coat finish with SS trim
• RoHS Compliant
• Auxiliary (additional) limit switches
Engineering Specifications
Size: S92, A92, B92, C92
Torque: 400-2000 in/lbs
Voltage: 120 VAC 1Ph 50/60 Hz
Amp Draw: S92, B92 .5A, A92 .8A, C92 1.0A
Conduit Entry: Two (2) 1/2" NPT
Max Ambient Temperature: 150º F
Switches: Two (2) single pole, double throw (2SPDT)
15 amp rated
Cycle Time per 90º: S92, A92: 15 seconds* Approx.
tt
B92, C92: 32 seconds* Approx.
24 VDC
Amp
Duty
Draw
Cycle
12 VAC
Amp
Duty
Draw
Cycle
24 VAC
Amp
Duty
Draw
Cycle
Cycle Time per
90 Degrees
(seconds)*
Weight
(lbs)
S92
400
0.5
100%
0.4
100%
2.0
75%
4.0
75%
2.0
75%
3.0
75%
15
15.3
A92
700
0.8
75%
0.6
75%
2.0
75%
4.0
75%
2.0
75%
3.0
75%
15
15.3
B92
1100
0.5
100%
0.4
100%
2.0
75%
4.0
75%
2.0
75%
3.0
75%
32
15.3
C92
2000
1.0
50%
0.6
50%
2.0
75%
4.0
75%
2.0
75%
3.0
75%
32
18.3
Note: Amp rating is considered locked rotor. Duty cycles are for ambient temperature (73º F).
* Cycle times are approximate.
172
ASAHI/AMERICA
Rev. G 6-14
"