RF Admittance Level Measurement RXL Series, IntelliPoint0 pages
DREXELBROOK
®
A Leader In Level Measurement Solutions
IntelliPoint RF Series
Point Level Switch
One of the Drexelbrook RF Point Level
Switches You Won't Have to Calibrate
Simply install the IntelliPoint RF Series into the
tank and apply power…that's it! Unlike other RF
or capacitance systems that require calibration
via setpoint potentiometers, jumpers, magnets,
or pushbuttons, the IntelliPoint RF Series reliably
detects the absence or presence of material without
any adjustments.
The IntelliPoint RF Series software continuously
monitors the application for changes in composition,
dielectric or conductivity, and maintains a repeatable
trip point on the probe. Other RF and capacitance
systems require calibration adjustments when the
process material is changed. Since the the IntelliPoint
RF Series recognizes changes in material, it is ideal
for non-dedicated tanks that are used for a wide
variety of products.
Universal Power Supply
Intelligent Electronics
•t No calibration or setpoint adjustments.
•t Ignores changes in dielectric or conductivity.
•t Automatically recognizes and ignores coatings to
prevent false alarms.
•t Continuous self-test monitors circuits and sensing
elements for faults.
•t Universal power supply automatically detects input
power source.
Diverse Applications
•t Detects the absence or presence of liquids, slurries,
interfaces and granulars.
Output
•t (2) SPDT relays; relay#2 can be configured as an
alarm or fault.
Dual Compartment Housing
•t Power Supply is isolated from intrinsically-safe
sensing element and circuit board.
Remote or Integral Electronics
•t Unlike many technologies, electronics can be
remote mounted to a convenient or safe location
The IntelliPoint electronics use a universal power
supply module that can be powered from a 85 to
250 Vac or 21 to 100 Vdc supply without moving
jumpers.
Self-Test Feature
Automatic and manual test functions ensure
proper system operation. An AutoVerify™ selfcheck circuit continuously monitors that the
complete system is functioning properly. The Manual
Certify not only checks the function of the system,
but also checks the AutoVerify self-test circuits to
make sure that they are also working properly.
Dual Compartment Housing
New dual compartment housing separates the
customer wiring and power supply from the sensing
element and operating circuits. The encapsulated
power supply/terminal block design eliminates the
possibility of damage caused by moisture in the
conduit.