Model C2175A PT1000C 24Vdc PSU/Battery Charger0 pages
PT1000C PSU/Charger
Model C2175A (500 mA load/500mA Charge) Power Supply/ Battery Charger
• A Complete solution for small
battery-backed dc instrument
power systems.
•
Supply 12Vdc or 24Vdc systems
with continuous power during ac
line interruptions without the need
for inverters or mains UPS’s
• Ideal for RTU’s, dataloggers,
remote field instrumentation,
alarm systems, remote access
systems etc.
Features
•
•
•
•
•
•
•
DIN Rail mounting
Available in 12Vdc or 24Vdc output versions.
Operates from 85-264Vac universal ac supply
500 mA load plus 500mA charge current
Under-voltage cutout to protect battery from deep
discharge.
Charging characterised for sealed lead-acid cells.
Independently current limited battery charging for
optimum battery life.
OVERVIEW
The PT1000C is a combined Power Supply and Battery
Charger system with integrated standby battery
management for small uninterruptable instrument supply
applications.
Just connect mains supply, standby battery and load for
an industrial grade standby power supply system.
This DIN rail mounted product is ideal for providing dc
power to instrument systems where battery backup is
necessary to ensure continuous system operation during
power failure. Applications include RTU’s, dataloggers,
remote field instruments, alarm systems and access
controllers.
Managing battery-backed systems for optimum backup
time and battery life can be tricky and expensive.
This product incorporates many features that make
installing such systems simple and foolproof.
Copyright Omniflex ♦ Subject to change without notice
Datasheet DSC2175AR04 sheet 1 of 4
•
•
•
•
•
Over-current protection to protect wiring against
faults.
Charger shutdown input for battery testing.
AC detect output for mains monitoring.
Temperature compensated for optimum battery
float voltage control in wide ambient operating
environments.
Independent battery and load terminals for ease of
installation.
PROTECTION
Batteries are capable of delivering enormous currents
under system fault conditions that can damage wiring
and equipment. The PT1000C incorporates an autoresettable load cutout, which disconnects the load under
over-current fault condition.
During prolonged power outages, the back-up battery will
eventually discharge. If the load remains connected, the
battery enters its “deep” discharge phase, which can
cause irreparable damage to the battery, and reduce its
capacity and life. The PT1000C incorporates an undervoltage cutout that disconnects the load when the battery
voltage begins to fall.
Batteries can be kept on continuous charge as long as
the charging current and float voltage are kept below
their specified maximum values. The maximum charging
current is based upon the Ampere-hour capacity of the
battery. This is can be less than the rated load current
http://www.omniflex.com
©