HRT1
Rate Indicator/Totalizer with HART®
Communication Protocol
Product Bulletin HRT 1-111B
The Turbine Flowmeter Company
♦
♦
♦
♦
♦
♦
♦
♦
♦
♦
♦
HART® Field Communication Protocol.
5 Digit Rate, 8 Digit Totalizer LCD display with
configurable decimal point location.
8 Digit, Non-resettable Grand Total display.
Pulse Input supports turbine as well as many other pulse
generating flowmeters.
4-20mA Analog Output.
Up to 20 Point Linearization.
Optional Scaled Pulse Output representing an increment
of volume for each pulse.
Two Optional Alarm Outputs configurable for Rate and
Total.
Magnetically operated reed switch for Total reset.
Internal battery backup.
Configuration and Grand Total stored in non-volatile
memory. Grand Total saved once per minute.
Featuring 5 digits of rate and 8 digits of total, the HRT1 is a loop powered indicator capable of accepting
magnetic pickup, DC pulse or switch closure inputs. The HRT1 uses the 4-20mA loop to provide power
when this output is used and to provide the HART® communication link.
GENERAL
Linearization: Up to 20 points.
TOTAL DISPLAY:
8 Digits 0.26” high. Resettable.
Decimal Points: Configurable for 0, .0, .00 or .000
for rate and total.
Total Units: GAL, LIT, FT3, M3, BBL &“blank”.
Accuracy: Total: ±1 count, Rate: ±0.01%
GRAND TOTAL:
INPUTS
8 Digits 0.26” high, Non-resettable. Value stored once
per minute in non-volatile memory. Grand Total is
displayed for 15 seconds after pressing the > button.
Magnetic Pickup:
RATE DISPLAY:
5 Digits 0.5” High, Display updates once every two
seconds.
Rate Units: /SEC, /MIN, /HR, & /DAY.
K-factor: The pulses per unit of Total (e.g. pulses/gallon)
are configurable in the range 0.001 to 99,999,999.
Frequency Range: 0.2 Hz to 5000 Hz.
Signal Level: 30 mVp-p to 30Vp-p.
Opto-Isolated DC Pulse:
Frequency Range: 0 Hz to 5000 Hz.
Signal Type: DC Pulse.
High (Logic 1): 4 to 30 VDC
Low (Logic 0): <1 VDC
Min Pulse Width: 0.1 msec