Intelligent Touch Controller0 pages
Specifications
INTELLIGENT TOUCH CONTROLLER
DIII-NET PLUS ADAPTER
Reference
DCS601C71t
DCS601A72
Power Supply
Externally supplied AC24V, 50/60Hz
AC24V, 60Hz ± 10%
10 W maximum
5 W maximum
Power consumption
Operating condition
Surrounding temperature
32° F to 104° F
14° F to 104° F
Humidity
Less than 85% RH (non condensing)
20% to 90% RH (non condensing)
Dimensions
HxWxD
LCD panel
Maximum number of indoor units
size / # of dots / # of colors
inches 5-25/32 x 9-1/16 x 4-7/32
—
64 groups (maximum 128 indoor units)t
Use in conjunction with DCS601C71 to connect
an additional 64 groups (maximum 128 indoor units)
10
Maximum number of outdoor units
Input
Communication functions
7-15/32 x 6-3/16 x 1-21/32
5.7 inches / QVGA 320x240 / 4,096 colors
10
Touch panel
10 bit encoded analog inputt
Dlll-NET x 1
Air conditioning equipment communication line
—
Air conditioning equipment communication line
10BASE-T
Web option
—
PCMCIA slot
Flash memory card used for PDD
—
RS232C
Input terminals
—
Digital input Di x 1
Overseas certification
Project data and engineering
Interface to i-Touch Controller
Forced shutdownt
F1-F2 x 1
—
—
Pulse input Pi x 3
DIII-NET connection to VRV outdoor units
Power measuring pulse
Interference (EMC)
Communication Capabilities via a Touch Screen or a Web Browser
Further Expand Air-Conditioning Control Possibilities.
1 pulse at 1 or 10 kWh and 40-400 msec
FCC Part 15 Subpart B Class A
FCC Part 15 Subpart B Class A
Configuration and engineering for each project
are necessary.
For further details, please consult with Daikin
distributors and dealers.
Configuration and engineering for each
project are necessary.
For further details, please consult with
Daikin distributors and dealers.
COMMENTS
Accessories
DESCRIPTION
REFERENCE
COMMENTS
Software
DCS002A71
Power Proportional Distribution (PPD)*
E-mail / Web software
—
Installation box
KJB411A
For wall mounted installation
—
Interface adapters
KRP928B2S
For connection to Split units
—
Digital input
Digital input/output
DEC101A51-US
DEC102A51-US
Input contacts: 8 inputs + 8 alarm inputs
Input contacts: 8 inputs + 8 alarm inputs
Input contacts: 4 inputs + 4 alarm inputs
Output contacts: 4 outputs
Input contacts: 4 inputs + 4 alarm inputs
Output contacts: 4 outputs
Connector cable
RS232C
Connectable up to
128 Indoor Unit Groups
(256 indoor units)
Control Daikin Systems
Remotely
Centralized monitoring control
system based on a Web
browser (Optional)
—
DCS004A71
More Freedom to Administrators
—
32-foot connector cable (included)
kWh meter
ITEM
kWh meter
REQUIREMENT SPECIFICATION
Pulse transmitter – 1 Pulse to 1kW or 10 kW pulse width must be between 40 - 400 msec
– Output relay must be electronic type only.
– No voltage output
© 2008 Daikin Industries, Limited.
Daikin® Daikin® AC are trademarks pending or registered trademarks of Daikin Industries, Limited. All rights reserved.
,
The air conditioners manufactured
by Daikin Industries have received
ISO 9000 series certification for
quality assurance.
Certificate Numbers:
(ISO9001)t JMI-0107t
t
JQA-1452
(ISO9002) JQA-1452
All Daikin Industries locations and
subsidiaries in Japan have received
environmental management system
standard ISO 14001 certification.
Daikin Industries, Ltd.
Domestic Group
Certificate Number: EC99J2044
About ISO 14001
ISO 14001 is the standard defined by the International
Organization for Standardization (ISO) relating to
environmental management systems. Our group has
been acknowledged by an internationally accredited
compliance organization as having an appropriate
program of environmental protection procedures and
activities to meet the requirements of ISO 14001.
Daikin AC (Americas), Inc.
1645 Wallace Drive, Suite 110
Carrollton, TX 75006 USA
www.daikinac.com
info@daikinac.com
866-4DAIKIN
(972) 245-1510
Dealer Information
PCITUSE08-09C
– aikin’s products are subject to continuous improvements. Daikin reserves the right to modify product design, specifications and information in this brochure without notice and without incurring any obligations.
D
* he Power Proportional Distribution (PPD) feature supplies the user with a reasonably calculated apportionment of the total power consumption by the Daikin air-conditioning system to individual units on the system. Because input to the
T
PPD includes measured pulses in the refrigerant system and because the air-conditioning system includes a number of variables, including operating temperatures and pressures, piping length, heat exchange rates and others, no meter-type
apportionment of individual users’ consumption can be made. However, the PPD feature provides an apportionment methodology that uses highly advanced technology as applied to the many variables in an air-conditioning system.
Malfunction Reports
to a Mobile Phone,
Anywhere
Malfunction reports
delivered by e-mail
(Optional)