SEL-2414 Transformer Monitor0 pages
SEL-2414 Transformer Monitor
Complete System for Control and Monitoring
Major Features and Benefits
The SEL-2414 Transformer Monitor provides an exceptional combination of monitoring, control, and communications
in a compact package.
➤ High Reliability, Rugged Design, and Low Price. Apply the SEL-2414 in harsh physical and electrical environments. The SEL-2414 withstands vibration, electrical surges, fast transients, extreme operating temperatures from
–40° to +85°C, and meets stringent utility standards. Compare our superior specification compliance, higher reliability, lower price, and worldwide, ten-year warranty to other transformer monitor alternatives.
➤ Flexible I/O for Transformer Status, Alarms, and More. Input/output options include digital inputs for status
such as oil level and sudden pressure; RTD and thermocouple inputs for measurements such as ambient, top-oil,
and hot-spot temperatures; digital outputs for control and alarms; analog inputs and outputs; and ac current and
voltage inputs. Easily program monitoring and control functions with powerful logic, math, timers, counters, and
edge-trigger functions. These features allow easy integration with new and retrofit transformer monitor applications. Monitor critical substation assets with comprehensive transformer thermal and through-fault monitoring.
➤ Advanced Asset Monitoring. Monitor critical substation assets with comprehensive transformer thermal and
through-fault monitoring. Calculate top oil, hotspot, insulation aging acceleration factor, and loss of life while generating hourly and daily data about your transformer. Capture through-fault current data that could lead to
increased transformer wear.
➤ Critical Reporting and Logging. Store up to 512 Sequential Events Recorder (SER) reports of digital input transitions, time-tagged to the nearest millisecond. Analyze SER reports, analog trending and oscillographic event
reports for rapid commissioning, testing, and post-event diagnostics. Send the SER data to a communications processor or computer for system analysis.
➤ Communications and Integration. Automate fan bank control with flexible communication options that provide
easy integration with SCADA. Choose from single and dual Ethernet, Modbus® TCP, DNP3 LAN/WAN,
IEC 61850, Modbus Serial, EIA-232, EIA-485, Telnet, and File Transfer protocols.
Schweitzer Engineering Laboratories, Inc.
SEL-2414 Data Sheet
"