DCC Dual Channel Controller0 pages
Self Contained - {NEW PRODUCT: COMING SOON}
DCC Dual Channel System
technical drawing
8.6in
4.3in
DR AFT
10.0in
The DCC Dual Channel Controller is a self contained system that offers
one or two channel configurations for monitoring toxic, combustible
and refrigerant gases with straightforward control functionality for
non-hazardous, non-explosion rated, commercial applications.
Sensor configurations include, two internal electrochemical sensors (one
must be CO), or one internal electrochemical and one remote catalytic
or remote solid state sensor or a remote 4-20 mA transmitter. Other
features include two 4 - 20 mA outputs and one optional 4 - 20 mA
input, two alarm level line voltage relays with field configurable time
delays and trigger levels, a field selectable integral audible alarm and an
LCD/LED panel indicating channel alarm status and fault conditions. An
optional extra loud buzzer is available for noisy environments.
Automated calibration and other maintenance procedures are simple
and easily performed in the field. For parking garage applications, our
proprietary Calibration Extending Firmware (CEF) takes into account
the aging of the toxic gas sensors so that less frequent calibrations are
required.
KEY FEATURES
» Single or dual channel operation
» Flexible internal and remote sensor configurations
» Six conduit entry ports
» Thermal resetting fuse
» Two line LCD display with embedded LED indicators
» Two 5-amps SPDT dry contact relays
» Optional extra loud buzzer
» Optional 4 - 20 mA input
» Two 4- 20 mA outputs
» Standard water / dust tight, corrosion resistant enclosure (drip proof);
IP54 certified with optional splash guard installed
technical specifications
GAS TYPE
Carbon Monoxide (CO), Nitrogen Dioxide
(NO2), Nitric Oxide (NO), Ethylene (C2H4),
Oxygen (O2)
Refrigerants
R22, R134A, R402A, R404A, R407C, R410A,
(remote)
R422D, R507A
Combustible (catalytic) Hydrogen (H2), Methane (CH4),
(remote)
Propane (C3H8)
TVOCs (solid state) (remote)
Electrochemical
(internal)
MECHANICAL
Enclosure
Weight
Size
ELECTRICAL
Power Requirement
Low Voltage 16 - 30 VDC or 12 - 28 VAC, 10 W, Class 2
Line Voltage 90 - 240 VAC, 50 - 60 Hz
Current Draw
Low Voltage 400 mA @ 24 VDC (400 mA RMS @ 24 VAC)
Line Voltage (110 VAC) Approximately 90 mA
Line Voltage (220 VAC) Approximately 45 mA
Wiring
24 VDC or 24 VAC two-conductor shielded;
VAC (line voltage) three-conductor shielded
Circuit
ARM Cortex based analog signal processing
board with jumpers for user interface.
Distance
Maximum 500 ft between controller and
remote solid state sensor using minimum
18 gauge wire stranded within conduit.
Reference the manual for maximum distances to maintain for remote transmitters.
Fuse
Automatic resetting thermal
APPLICATIONS
» Parking Garages
» Firehalls
» Commerical Swimming Pools
» Arenas
» Wineries
» Fisheries
» ... and many more
ABS / Polycarbonate, rated UL94-5VA; IP54
certified with splash guard installed
600 g (1.4 lb)
10.0” x 8.6” x 4.3”
(254 mm x 218 mm x 109 mm)
© 2015 Critical Environment Technologies Canada Inc. | Data subject to change without notice. | Toll Free: +1.877.940.8741 | www.critical-environment.com
"